Troubleshooting by Indication on the Remote Controller
SiBE37-701
336
Troubleshooting
3.49
“
U5
”
Indoor Unit:
Malfunction of Transmission between
Remote Controller and Indoor Unit
Remote
Controller
Display
U5
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Malfunction of indoor unit remote controller transmission
Connection of two main remote controllers (when using 2 remote controllers)
Defect of indoor unit PC board
Defect of remote controller PC board
Malfunction of transmission caused by noise
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2823)
NO
NO
NO
YES
NO
Replace indoor unit PC
board.
Set one remote controller to
"SUB"; turn the power supply
off once and then back on.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
Normal
Normal
NO
NO
Using
2-remote controllers
control.
All indoor
PC board microcomputer
monitors blink.
Operation
returns to normal when
the power is turned off
momentarily.
YES
YES
YES
SS1 of
both remote controllers
is set to "MAIN."
Replace the remote controller
Normal
YES
Replace the indoor unit PC
board.
Normal
YES
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...