SiBE37-701
Troubleshooting by Indication on the Remote Controller
Troubleshooting
355
3.56
“
UF
”
System is not Set yet
Remote
Controller
Display
UF
Applicable
Models
All models of indoor units
REYQ8P~48P
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
The malfunction is determined as soon as the abnormality aforementioned is detected through
checking the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Failure to execute check operation
Defect of indoor unit PC board
Stop valve is left in closed
Troubleshooting
Note:
Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2830)
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
Replace indoor unit PC board.
Wiring check operation may
not have been carried out
successfully.
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
∗
The unit will not run for up to
12 minutes.
YES
NO
YES
NO
NO
YES
Is the
check operation
carried out?
Is indoor
-outdoor and outdoor-
outdoor unit transmission
wiring normal?
Open stop valve.
YES
NO
Are the stop
valves openned?
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...