SiUS34-907
Troubleshooting by Remote Controller
Troubleshooting
103
k
: ON
h
: OFF
l
: Blink
Malfunction
code
Operation
lamp
Malfunction contents
Page
Referred
Indoor Unit
A0
l
Error of External Protection Device
109
A1
l
PCB Defect
110
A3
l
Malfunction of Drain Level Control System (S1L)
111
A6
l
Fan Motor (M1F) Lock, Overload
113
115
116
A7
k
Malfunction of Swing Flap Motor (M1S)
119
A9
l
Malfunction of Moving Part of Electronic Expansion Valve (Y1E)
121
AF
k
Drain Level above Limit
123
AJ
l
Malfunction of Capacity Determination Device
124
C4
l
Malfunction of Thermistor (R2T) for Heat Exchanger
125
C5
l
Malfunction of Thermistor (R3T) for Gas Pipes
126
C9
l
Malfunction of Thermistor (R1T) for Suction Air
127
CJ
k
Malfunction of Thermostat Sensor in Remote Controller
128
Outdoor Unit
E1
l
PCB Defect
129
E3
l
Actuation of High Pressure Switch
130
E4
l
Actuation of Low Pressure Sensor
133
E5
l
Inverter Compressor Motor Lock
135
E6
l
STD Compressor Motor Overcurrent/Lock
—
E7
l
Malfunction of Outdoor Unit Fan Motor
138
E9
l
Malfunction of Moving Part of Electronic Expansion Valve (Y1E, Y2E)
141
F3
l
Abnormal Discharge Pipe Temperature
143
F6
l
Refrigerant Overcharged
145
H3
k
Failure of High Pressure Switch
—
H4
l
Actuation of Low Pressure Switch
—
H7
l
Abnormal Outdoor Fan Motor Signal
—
H9
l
Malfunction of Thermistor (R1T) for Outdoor Air
146
J2
l
Current Sensor Malfunction
—
J3
l
Malfunction of Discharge Pipe Thermistor (R2T)
147
J5
l
Malfunction of Thermistor (R3T, R5T) for Suction Pipe
148
J6
l
Malfunction of Thermistor (R4T) for Outdoor Unit Heat Exchanger
149
J7
l
Malfunction of Liquid Pipe Thermistor (R7T)
150
J9
l
Malfunction of Subcooling Heat Exchanger Gas Pipe Thermistor (R6T)
151
JA
l
Malfunction of High Pressure Sensor
152
JC
l
Malfunction of Low Pressure Sensor
154
L0
l
Inverter System Error
—
L1
l
Malfunction of PCB
157
L4
l
Malfunction of Inverter Radiating Fin Temperature Rise
159
L5
l
Inverter Compressor Abnormal
162
L8
l
Inverter Current Abnormal
164
L9
l
Inverter Start up Error
166
LA
l
Malfunction of Power Unit
—
P1
l
Inverter Over-Ripple Protection
169
P4
k
Malfunction of Inverter Radiating Fin Temperature Rise Sensor
171
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...