Specifications
Specifications
15
Ceiling Suspended Type
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXHQ12MVJU
FXHQ24MVJU
FXHQ36MVJU
1 Cooling Capacity
Btu/h
12,000
24,000
36,000
2 Heating Capacity
Btu/h
13,500
27,000
40,000
Casing / Color
White(10Y9/0.5)
White(10Y9/0.5)
White(10Y9/0.5)
Dimensions: (H×W×D)
in. (mm)
7-11/16 × 37-13/16 × 26-3/4
(195 x 960 x 679)
7-11/16 × 55-1/8 × 26-3/4
(195 x 1400 x 679)
7-11/16 × 62-5/8 × 26-3/4
(195 x 1591 x 679)
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2×12×15
3×12×15
2×12×15+2×10×15
Face Area
ft² (m²)
1.96 (0.6)
3.15 (1.0)
3.66 + 2.95 (1.1 + 0.9)
Fan
Model
3D12K1AA1
3D12K2AA1
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output
W
62
130
130
Airflow Rate (H/L)
cfm
410/340
710/600
830/670
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Sound Absorbing Thermal Insulation Material
Glass Wool
Glass Wool
Glass Wool
Air Filter
Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes
in. (mm)
φ
1/4 (6.4) (Flare Connection)
φ
3/8 (9.5) (Flare Connection)
φ
3/8 (9.5) (Flare Connection)
Gas Pipes
in. (mm)
φ
1/2 (12.7) (Flare Connection)
φ
5/8 (15.8) (Flare Connection)
φ
5/8 (15.8)(Flare Connection)
Drain Pipes
in. (mm)
VP20
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
VP20
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
VP20
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
Machine Weight (Mass)
Lbs (kg)
55 (25)
80 (36)
90 (41)
4 Sound Level (H/L)
dBA
42
44
46
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A Series
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Drawing No.
C:4D049326
(
)
(
)
(
)
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...