SiUS34-907
Basic Control
Function
35
2.4
Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the adequate amount of
circulation air with liquid pressure secured by high pressure control using the outdoor unit fan.
When the outdoor temperature
≥
68°F, the compressor will run in Step 7 or higher.
When the outdoor temperature
≥
64°F, it will run in Step 5 or higher.
When the outdoor temperature
≥
54°F, it will run in Step 1 or higher.
850 rpm
715 rpm
580 rpm
445 rpm
360 rpm
285 rpm
400 rpm
250 rpm
0 rpm
M1F
815 rpm
680 rpm
545 rpm
410 rpm
325 rpm
250 rpm
0 rpm
0 rpm
0 rpm
M2F
STEP 3
STEP 4
STEP 5
STEP 6
STEP 7
STEP 8
STEP 2
STEP 1
STEP 0
Cooling
Fan Steps
Upper limit of fan
revolutions: STEP 8
Upper limit of outdoor unit
fan revolutions
STEP 7
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
Pc
<399 psi
PI control
Pc
>470 psi
Lapse of 20 sec.
PI control
PI control
Lapse of 20 sec.
Hold the
current step on
outdoor unit fan
Pc: High pressure sensor detection value
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...