• Outdoor Unit • VRV

®

III heat recovery, with connection to heating only hydrobox • REYAQ-P

• VRV

®

 Systems • Outdoor Unit

4

1

Specifications

 Notes

 (1) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; 100% connection ratio (DX indoor units); For combination with HXHD125, cf. capacity table
 (2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; 100% connection ratio (DX indoor units); For combination with HXHD125, cf. capacity table
 (3) Ssc: Short-circuit power
 (4) In case of connection with a 20~50 type indoor unit, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be 

brazed.

 (5) In case the joint diameter does not fit on the triple piping side, a reducer is needed (field supply)
 (6) Insulators are necessary (field supply) for the triple piping side
 (7) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
 (8) Maximum allowable voltage range variation between phases is 2%.
 (9) MCA/MFA: MCA = 1.25 x FLA
 (10) MFA 

 4 x FLA

 (11) Next lower standard fuse rating minimum 15A
 (12) Select wire size based on the value of MCA
 (13) Instead of a fuse, use a circuit breaker
 (14) In case of connecting with indoor unit capacity index between 150 and 160, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and 

the field pipe must be brazed.

 (15) In case of connecting with a 200 type indoor unit or capacity index more than 160 and less than 200, match to the size of the field pipe using the attached pipe. Connection between 

the attached pipe and the field pipe must be brazed.

1-2 Electrical Specifications

REYAQ10P

REYAQ12P

REYAQ14P

REYAQ16P

Power supply

Phase

3~

Frequency

Hz

50

Voltage

V

380-415

Voltage range

Min.

%

-10

Max.

%

6

Current

Zmax

Text

0.27

-

Current - 50Hz Maximum running current

A

22.1

22.3

32.8

33

Starting current (MSC)

A

74

75

-

Minimum Ssc value

kVa

843

850

2,045

2,035

Maximum fuse amps (MFA)

A

25

40

Wiring connections 
- 50Hz

For power supply

Quantity

4G

Remark

Select diameter and type according to national and local regulations

For connection with indoor

Quantity

2G

Remark

F1,F2

Power supply intake

Both indoor and outdoor unit

Summary of Contents for VRV III

Page 1: ...REYAQ P E E D E N 1 1 2 0 0 Air Conditioners VRV III heat recovery with connection to heating only hydrobox Technical Data...

Page 2: ...REYAQ P E E D E N 1 1 2 0 0 Air Conditioners VRV III heat recovery with connection to heating only hydrobox Technical Data...

Page 3: ...s 7 Cooling Capacity Tables 7 Heating Capacity Tables 15 Capacity Correction Factor 23 5 Dimensional drawings 27 Dimensional Drawings 27 6 Centre of gravity 28 Centre of Gravity 28 7 Piping diagrams 2...

Page 4: ...765 Packed unit Height mm 1 885 Width mm 1 425 Depth mm 860 Weight Unit kg 331 339 Packed unit kg 339 347 Packing Material Cardboard Wood EPS Cardboard Wood EPS Cardboard Wood EPS Cardboard Wood EPS W...

Page 5: ...2 Piping length OU IU Max m 100 After branch Max m 40 Total piping length System Actual m 300 Level difference OU IU Outdoor unit in highest position m 40 Indoor unit in highest position m 40 IU IU Ma...

Page 6: ...n phases is 2 9 MCA MFA MCA 1 25 x FLA 10 MFA 4 x FLA 11 Next lower standard fuse rating minimum 15A 12 Select wire size based on the value of MCA 13 Instead of a fuse use a circuit breaker 14 In case...

Page 7: ...LWDO 3UHVVXUH JDXJH NLW 2 2 2 2 2QO DYDLODEOH IRU LQGLYLGXDO 694 ER HV QRW SRVVLEOH IRU HQWUDO 69 4 69 4 0XOWL WHQDQW LV SRVVLEOH 1HHG FRQQHFW RSWLRQ 3 7 WR HDFK 694 ER QHHG FRPSDWLEOH LQGRRU XQLW OOR...

Page 8: ...HU LQSXW UHTXLUHG WR RSHUDWH WKH FDVFDGH V VWHP IUDFWLRQ RI RXWGRRU XQLW SRZHU LQSXW FDVFDGH VWHS SRZHU LQSXW D DVFDGH VWHS SRZHU LQSXW E QWHJUDWHG KHDWLQJ FDSDFLW DQG FDSDFLW FDOFXODWLRQ LQGH FRUUHFW...

Page 9: ...46 33 5 5 51 34 3 5 56 23 22 7 3 53 27 0 4 54 31 4 5 65 31 8 5 68 32 2 5 71 33 0 5 76 33 8 5 81 25 22 7 3 78 27 0 4 85 30 9 5 90 31 3 5 93 31 7 5 96 32 6 6 01 33 4 6 07 27 22 7 4 03 27 0 5 19 30 5 6 1...

Page 10: ...0 3 61 16 13 2 1 79 15 8 2 13 18 3 2 49 19 6 2 68 20 9 2 87 23 4 3 27 26 0 3 68 18 13 2 1 82 15 8 2 17 18 3 2 54 19 6 2 73 20 9 2 93 23 4 3 33 26 0 3 75 20 13 2 1 85 15 8 2 21 18 3 2 59 19 6 2 78 20...

Page 11: ...71 40 0 6 77 41 0 6 84 23 27 1 4 35 32 4 5 58 37 5 6 95 38 0 6 99 38 5 7 02 39 5 7 09 40 5 7 15 25 27 1 4 65 32 4 5 97 37 0 7 26 37 5 7 29 38 0 7 33 38 9 7 40 39 9 7 47 27 27 1 4 96 32 4 6 38 36 4 7 5...

Page 12: ...1 4 44 16 15 8 2 20 18 9 2 62 21 9 3 07 23 5 3 30 25 0 3 53 28 0 4 02 31 1 4 53 18 15 8 2 24 18 9 2 67 21 9 3 12 23 5 3 36 25 0 3 60 28 0 4 10 31 1 4 62 20 15 8 2 27 18 9 2 71 21 9 3 18 23 5 3 42 25...

Page 13: ...42 49 7 9 50 50 8 9 58 23 32 4 5 68 38 6 7 29 44 9 9 11 47 2 9 80 47 8 9 85 49 0 9 93 50 1 10 0 25 32 4 6 07 38 6 7 81 44 9 9 76 46 5 10 2 47 1 10 3 48 3 10 4 49 5 10 5 27 32 4 6 48 38 6 8 35 44 9 10...

Page 14: ...1 5 81 16 18 9 2 88 22 5 3 42 26 2 4 01 28 0 4 31 29 8 4 62 33 5 5 26 37 1 5 92 18 18 9 2 92 22 5 3 48 26 2 4 08 28 0 4 39 29 8 4 71 33 5 5 36 37 1 6 03 20 18 9 2 97 22 5 3 55 26 2 4 16 28 0 4 48 29...

Page 15: ...1 7 55 9 11 8 57 2 11 9 23 36 4 7 03 43 5 9 02 50 5 11 3 53 2 12 1 53 8 12 2 55 1 12 3 56 5 12 4 25 36 4 7 51 43 5 9 66 50 5 12 1 52 4 12 7 53 1 12 7 54 4 12 8 55 7 13 0 27 36 4 8 02 43 5 10 3 50 5 12...

Page 16: ...7 7 18 16 21 3 3 56 25 4 4 24 29 5 4 96 31 5 5 33 33 5 5 71 37 6 6 50 41 7 7 32 18 21 3 3 61 25 4 4 31 29 5 5 05 31 5 5 43 33 5 5 82 37 6 6 63 41 7 7 46 20 21 3 3 68 25 4 4 39 29 5 5 14 31 5 5 54 33...

Page 17: ...5 7 66 24 4 7 92 24 4 8 05 24 4 8 18 24 3 8 44 9 5 10 0 25 1 7 52 25 1 7 77 25 0 8 02 25 0 8 15 24 9 8 27 24 9 8 53 8 5 9 1 25 7 7 62 25 6 7 86 25 6 8 11 25 5 8 23 25 5 8 36 25 4 8 60 7 0 7 6 26 6 7...

Page 18: ...0 6 7 98 19 2 7 32 9 8 11 0 24 2 9 06 23 5 8 82 22 1 8 17 21 3 7 86 20 6 7 54 19 2 6 93 9 5 10 0 24 7 9 13 23 5 8 57 22 1 7 94 21 3 7 63 20 6 7 33 19 2 6 74 8 5 9 1 24 9 8 96 23 5 8 34 22 1 7 73 21 3...

Page 19: ...2 6 87 25 1 7 18 25 1 7 34 25 1 7 50 25 0 7 81 9 5 10 0 25 9 6 69 25 8 7 00 25 7 7 30 25 7 7 45 25 7 7 61 25 6 7 91 8 5 9 1 26 4 6 81 26 4 7 11 26 3 7 41 26 3 7 56 26 2 7 70 26 1 8 00 7 0 7 6 27 4 7...

Page 20: ...3 6 9 00 22 9 8 82 9 8 11 0 24 8 8 55 24 8 8 75 24 7 8 95 24 7 9 04 24 6 9 08 22 9 8 34 9 5 10 0 25 4 8 63 25 4 8 83 25 3 9 02 25 3 9 12 24 6 8 82 22 9 8 10 8 5 9 1 26 0 8 71 25 9 8 90 25 9 9 09 25 4...

Page 21: ...1 9 57 32 0 9 95 32 0 10 1 31 9 10 3 31 8 10 7 9 5 10 0 32 9 9 35 32 9 9 72 32 8 10 1 32 7 10 3 32 7 10 5 32 6 10 8 8 5 9 1 33 6 9 49 33 6 9 86 33 5 10 2 33 4 10 4 33 4 10 6 33 3 11 0 7 0 7 6 34 9 9...

Page 22: ...9 5 11 8 27 5 10 9 9 8 11 0 31 6 11 6 31 6 11 9 31 5 12 1 30 5 11 6 29 5 11 2 27 5 10 3 9 5 10 0 32 4 11 7 32 3 12 0 31 5 11 8 30 5 11 3 29 5 10 9 27 5 9 98 8 5 9 1 33 1 11 8 33 0 12 1 31 5 11 4 30 5...

Page 23: ...4 12 4 37 3 12 8 37 2 13 1 37 2 13 3 37 1 13 7 9 5 10 0 38 4 12 1 38 3 12 6 38 2 13 0 38 1 13 2 38 1 13 4 38 0 13 9 8 5 9 1 39 2 12 3 39 1 12 7 39 0 13 2 39 0 13 4 38 9 13 6 38 8 14 0 7 0 7 6 40 7 12...

Page 24: ...8 14 0 30 5 12 8 9 8 11 0 36 8 14 8 36 8 15 1 35 0 14 3 33 9 13 7 32 8 13 2 30 5 12 1 9 5 10 0 37 7 14 9 37 3 14 9 35 0 13 8 33 9 13 3 32 8 12 8 30 5 11 7 8 5 9 1 38 6 15 0 37 3 14 5 35 0 13 5 33 9 12...

Page 25: ...correction factor for capacity due to piping length to farest indoor unit Equivalent piping length correction 4 When overall equivalent piping length is 90m or more the diameter of the main liquid pi...

Page 26: ...correction factor for capacity due to piping length to farest indoor unit Equivalent piping length correction 4 When overall equivalent piping length is 90m or more the diameter of the main liquid pi...

Page 27: ...correction factor for capacity due to piping length to farest indoor unit Equivalent piping length correction 4 When overall equivalent piping length is 90m or more the diameter of the main liquid pi...

Page 28: ...correction factor for capacity due to piping length to farest indoor unit Equivalent piping length correction 4 When overall equivalent piping length is 90m or more the diameter of the main liquid pip...

Page 29: ...QHFWLRQ 5 4 3 6KRZV WKH GLPHQVLRQV DIWHU LQJ WKH DFFHVVRU EDJ 1R 3DUWV QDPH 5HPDUNV LTXLG SLSH FRQQHFWLRQ SRUW 6HH QRWH 6XFWLRQ JDV SLSH FRQQHFWLRQ SRUW 6HH QRWH LVFKDUJH JDV SLSH FRQQHFWLRQ SRUW 6HH...

Page 30: ...VRV Systems Outdoor Unit 28 6 Centre of gravity 6 1 Centre of Gravity 5 4 3 7 HQWHU RI IRXQGDWLRQ EROW KROH HQWHU RI IRXQGDWLRQ EROW KROH 6 27 HQWHU RI IRXQGDWLRQ EROW KROH 6 27 HQWHU RI IRXQGDWLRQ E...

Page 31: ...with connection to heating only hydrobox REYAQ P 7 Piping diagrams 7 1 Piping Diagrams 5 4 3 7 6723 9 9 7 6 59 3257 PP 5 211 7 21 48 3 3 7 5 7 6 5 6 3 3 68 7 21 6 3 3 67 66 19 66 5 5 5 17 5 8 725 2 6...

Page 32: ...7521 3 16 21 9 9 0 1 3 12 6 7 5 4 57 5 5 7521 3 16 21 9 9 5 6 a 6 386 87721 6 7 02 6 7 5 7851 7 67 5 6 7 4 53 5 9 56 3 6 7 7 21 5 8 7 3 3 7521 3 16 21 9 9 68 22 5 5 6 6725 855 17 6 1625 3 3 6a 6 62 12...

Page 33: ...27 6 6 9 9 8 86 9 3 3 5 7 5 3 5 7 68 7 21 6 9 3 66 6 9 3 66 8 86 5 7 1 3 3 5 7 48 a 12 6 7 5 55 7 25 8 86 7 9 3 3 5 7 6 5 7 68 7 21 12 6 7 5 7 685 625 5 3 3 3a 3 3 27 03 6 59 021 725 25 1 3 35 3 5 7...

Page 34: ...2QO IRU QRUPDO SRZHU VXSSO LQVWDOODWLRQ 3RVVLELOLW 3RVVLELOLW 3RVVLELOLW 2QO IRU EHQH W N K UDWH SRZHU VXSSO LQVWDOODWLRQ 9 9 HDUWK HQH W N K UDWH SRZHU VXSSO 9 9 HDUWK HQH W N K UDWH SRZHU VXSSO FRQW...

Page 35: ...ta 10 1 Sound Power Spectrum REYAQ10P 3TW59927 2A Sound power level dB Octave band center frequency Hz REYAQ12P 3TW59927 2A Sound power level dB Octave band center frequency Hz REYAQ14P 3TW59927 2A So...

Page 36: ...sound pressure level dB 0dB 0 0002 bar Octave band center frequency Hz Approximate threshold hearing for continuous noise Front side 1 m 1 5 m Scale 50 Hz A 60 C 67 3TW59927 1A REYAQ14P 3TW59927 1A N...

Page 37: ...pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply Selection of refrigerant branch kits Refrigerant refnets When using refnet joint...

Page 38: ...ht difference Difference in height between outdoor and indoor units H1 40 m Difference in height between lowest and heighest indoor unit H2 15 m Indoor unit capacity index Refrigerant branch kit name...

Page 39: ...UHD RPHVWLF KRW ZDWHU RSHUDWLRQ 6WDUWXS DUHD 2SHUDWLRQ SRVVLEOH EXW QR JXDUDQWHH RI FDSDFLW 2SHUDWLRQ SRVVLEOH EXW QR JXDUDQWHH RI FDSDFLW DQ EH DGMXVWHG E HOG VHWWLQJ REYAQ P 3TW60653 1A 2 Continuous...

Page 40: ...on the environment This challenge demands the eco design and development of a wide range of products and an energy management system resulting in energy conservation and a reduction of waste Daikin pr...

Reviews: