• Outdoor Unit • VRV
®
III heat recovery, with connection to heating only hydrobox • REYAQ-P
• VRV
®
Systems • Outdoor Unit
4
1
Specifications
Notes
(1) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; 100% connection ratio (DX indoor units); For combination with HXHD125, cf. capacity table
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; 100% connection ratio (DX indoor units); For combination with HXHD125, cf. capacity table
(3) Ssc: Short-circuit power
(4) In case of connection with a 20~50 type indoor unit, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and the field pipe must be
brazed.
(5) In case the joint diameter does not fit on the triple piping side, a reducer is needed (field supply)
(6) Insulators are necessary (field supply) for the triple piping side
(7) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(8) Maximum allowable voltage range variation between phases is 2%.
(9) MCA/MFA: MCA = 1.25 x FLA
(10) MFA
≤
4 x FLA
(11) Next lower standard fuse rating minimum 15A
(12) Select wire size based on the value of MCA
(13) Instead of a fuse, use a circuit breaker
(14) In case of connecting with indoor unit capacity index between 150 and 160, match to the size of the field pipe using the attached pipe. Connection between the attached pipe and
the field pipe must be brazed.
(15) In case of connecting with a 200 type indoor unit or capacity index more than 160 and less than 200, match to the size of the field pipe using the attached pipe. Connection between
the attached pipe and the field pipe must be brazed.
1-2 Electrical Specifications
REYAQ10P
REYAQ12P
REYAQ14P
REYAQ16P
Power supply
Phase
3~
Frequency
Hz
50
Voltage
V
380-415
Voltage range
Min.
%
-10
Max.
%
6
Current
Zmax
Text
0.27
-
Current - 50Hz Maximum running current
A
22.1
22.3
32.8
33
Starting current (MSC)
A
74
75
-
Minimum Ssc value
kVa
843
850
2,045
2,035
Maximum fuse amps (MFA)
A
25
40
Wiring connections
- 50Hz
For power supply
Quantity
4G
Remark
Select diameter and type according to national and local regulations
For connection with indoor
Quantity
2G
Remark
F1,F2
Power supply intake
Both indoor and outdoor unit