14 Piping installation

Installation and operation manual

20

RK RKXYQ8T7Y1B

VRV IV compressor unit for indoor installation

4P499900-1B – 2021.12

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

63~140

15.9

9.5

200

19.1

250

22.2

14.1.4

To select refrigerant branch kits

For piping example, refer to 

"14.1.3 To select the piping size"

 [

4

 19].

Refnet joint at first branch (counting from the compressor unit)

When  using  refnet  joints  at  the  first  branch  counted  from  the
compressor unit side, choose from the following table in accordance
with  the  capacity  of  the  compressor  unit. 

Example: 

Refnet  joint  c

(B→C/D).

Compressor unit capacity type

Refrigerant branch kit

5 HP

KHRQ22M20TA

8 HP

KHRQ22M29T9

Refnet joints at other branches

For refnet joints other than the first branch, select the proper branch
kit  model  based  on  the  total  capacity  index  of  all  indoor  units
connected  after  the  refrigerant  branch. 

Example: 

Refnet  joint  c

(C→D/D).

Indoor unit capacity index

Refrigerant branch kit

<200

KHRQ22M20TA

200≤x<260

KHRQ22M29T9

Refnet headers

Concerning  refnet  headers,  choose  from  the  following  table  in
accordance  with  the  total  capacity  of  all  the  indoor  units  connected
below the refnet header.

Indoor unit capacity index

Refrigerant branch kit

<260

KHRQ22M29H

INFORMATION

Maximum 8 branches can be connected to a header.

14.1.5

Refrigerant piping length and height
difference

The  piping  lengths  and  height  differences  must  comply  with  the
following requirements.

H1

H2

H3

H5

L1

a

L2

L3

L4

L5

L6

L7

H4

b

EKEXV

AHU

VRV DX

VRV DX

c

c

a

Heat exchanger unit

b

Compressor unit

c

Refrigerant branch kit

VRV DX

VRV DX indoor unit

EKEXV

Expansion valve kit

AHU

Air handling unit

H1~H5

Height differences

L1~L7

Piping lengths

Minimum and maximum piping lengths

1

Heat exchanger unit →
Compressor unit

L1≤30 m

2

Actual piping length (equivalent
piping length)

(a)

L2+L3+L4≤70 m (90 m)

L2+L5+L6≤70 m (90 m)

L2+L5+L7≤70 m (90 m)

3

Total piping length (x=L1+L2+L3+L4+L5+L6+L7)

Minimum

10 m≤x

Maximum in case of
8 HP

x≤300 m

Maximum in case of
5 HP

If

Then

L1≤30 m

x≤115 m

L1≤25 m

x≤120 m

L1≤20 m

x≤125 m

L1≤15 m

x≤130 m

L1≤10 m

x≤135 m

L1≤5 m

x≤140 m

4

EKEXV →

 

AHU

L4≤5 m

5

First branch kit → Indoor unit/
AHU

L3+L4≤40 m

L5+L6≤40 m

L5+L7≤40 m

Maximum height differences

(b)

1

Heat exchanger unit ↔
Compressor unit

H1≤10 m

2

Compressor unit ↔ Indoor unit H2≤30 m

H3≤30 m

3

EKEXV ↔

 

AHU

H4≤5 m

4

Indoor unit ↔ Indoor unit

H5≤15 m

(a)

Assume equivalent piping length of refnet joint=0.5 m and
refnet header=1 m (for calculation purposes of equivalent
piping length, not for refrigerant charge calculations).

(b)

Either unit can be the highest unit.

14.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

14.2.1

Using the stop valve and service port

To handle the stop valve

Take the following guidelines into account:

▪ Make sure to keep all stop valves open during operation.

▪ The gas and liquid stop valves are factory closed.

▪ Do  NOT  apply  excessive  force  to  the  stop  valve.  Doing  so  may

break the valve body.

To handle the service port

▪ Always  use  a  charge  hose  equipped  with  a  valve  depressor  pin,

since the service port is a Schrader type valve.

▪ After  handling  the  service  port,  make  sure  to  tighten  the  service

port  cover  securely.  For  the  tightening  torque,  refer  to  the  table
below.

▪ Check for refrigerant leaks after tightening the service port cover.

Summary of Contents for VRV IV i Series

Page 1: ...Installation and operation manual VRV IV compressor unit for indoor installation English Installation and operation manual VRV IV compressor unit for indoor installation RKXYQ5T8Y1B RKXYQ8T7Y1B...

Page 2: ...z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus nor...

Page 3: ...d senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t...

Page 4: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 5: ...door unit fan does not spin 15 8 2 15 Symptom The display shows 88 15 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 15 8 2 17 Symptom The inside of an...

Page 6: ...nstaller and user reference guide Preparation of the installation reference data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on http...

Page 7: ...rter A phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make...

Page 8: ...unsorted household waste If a chemical symbol is printed beneath the symbol this chemical symbol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols a...

Page 9: ...er such circumstances may cause breakage electrical shock or fire Contact your dealer WARNING The refrigerant in the system is safe and normally does NOT leak If the refrigerant leaks in the room cont...

Page 10: ...fter the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 6 2 3 About the heating operation It ma...

Page 11: ...only for double flow multi flow corner ceiling suspended and wall mounted Refer to 6 4 Adjusting the air flow direction 411 for details To stop 4 Press the ON OFF button on the user interface once aga...

Page 12: ...nsert fingers rods or other objects into the air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injury CAUTION After a long use check the unit stand a...

Page 13: ...or breaker is activated Change the fuse or reset the breaker if necessary Malfunction Measure If the system goes into fan only operation but as soon as it goes into heating or cooling operation the sy...

Page 14: ...on centralised control device indoor unit Auto address malfunction inconsistency Auto address malfunction inconsistency 8 2 Symptoms that are NOT system malfunctions The following symptoms are NOT sys...

Page 15: ...is the sound of refrigerant gas flowing through both indoor and outdoor units A hissing sound which is heard at the start or immediately after stopping operation or defrost operation This is the noise...

Page 16: ...quid 9 5 mm 9 5 mm e Piping adapter 19 1 22 2 mm that you need when connecting piping to the heat exchanger unit only for 8 HP 11 1 2 To remove the transportation stay Only for RKXYQ5 NOTICE If the un...

Page 17: ...s for the compressor unit and heat exchanger unit For more possible options see the installer and user reference guide Cool heat selector In order to control the cooling or heating operation from a ce...

Page 18: ...SK OF BURNING SCALDING DANGER RISK OF ELECTROCUTION 1 Remove the service cover of the compressor unit 5 5 5 HP 8 HP 2 If you want to make field settings remove the inspection cover 5 HP 8 HP 3 If you...

Page 19: ...ameters mm sizes taken the following into account Select the pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refr...

Page 20: ...unit b Compressor unit c Refrigerant branch kit VRV DX VRV DX indoor unit EKEXV Expansion valve kit AHU Air handling unit H1 H5 Height differences L1 L7 Piping lengths Minimum and maximum piping leng...

Page 21: ...B C C C D D RDXYQ RDXYQ c c d d b b a a 5 HP 8 HP Method 2 First connect to the first 2 service ports C C b B a A Then connect to the last 2 service ports d B c A C C a b c d Service ports of stop va...

Page 22: ...cause malfunctions smoke or fire 14 3 Checking the refrigerant piping 14 3 1 About checking the refrigerant piping Refrigerant piping works are finished The indoor units compressor unit and or heat ex...

Page 23: ...e splitters to both circuits and check Without refrigerant line splitters takes twice as long You have to check the circuits separately To do so First connect the manifold to circuit 1 and check Then...

Page 24: ...ing according to the installation environment Ambient temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm If there is a possibility that condensation on the stop valve might...

Page 25: ...C C d B c A a Liquid line stop valve circuit 1 to heat exchanger unit b Gas line stop valve circuit 1 to heat exchanger unit c Gas line stop valve circuit 2 to indoor units d Liquid line stop valve ci...

Page 26: ...unction code and take corresponding action 19 1 Solving problems based on error codes 438 14 4 5 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated gre...

Page 27: ...tween the compressor unit the heat exchanger unit and the indoor units Example g f F1 F2 16 V F1 F2 16 V 220 240 V 1 50 Hz e c a d b 220 240 V 1 50 Hz 380 415 V 3N 50 Hz a Main switch b Earth connecti...

Page 28: ...he left side of the switch box 1 c 50 mm a b b X1M L1 F1F2 L2 L3 N c a c X2M A1P b a X1M X2M 5 HP 50 mm a b b a X1M X1M A1P X1M b a c c 8 HP X1M A1P c a Transmission wiring b Power supply c Cable tie...

Page 29: ...ing components See 13 2 1 To open the compressor unit 418 16 1 3 Field setting components The components to make field settings differ depending on the model Model Field setting components 5 HP Push b...

Page 30: ...ot displayed after 10 12 minutes check the malfunction code on the indoor unit user interface and in case of 8 HP on the compressor unit 7 segment display Solve the malfunction code accordingly First...

Page 31: ...HP You can change the value of setting 2 8 Te target temperature during cooling operation to 4 8 C as follows Action Button display 1 Start from the default situation 2 Select mode 2 BS1 5 s 3 Select...

Page 32: ...1 16 Shows the 3rd last malfunction code 7 segments display Mode 1 in case of 8 HP You can read out the following information Setting Value Description 1 1 Shows the status of low noise operation 0 Un...

Page 33: ...ay and the settings differ depending on the model Model Display Setting value 5 HP 7 LEDs display The seven LEDs give a binary representation of the setting value number 8 HP 7 segments display The th...

Page 34: ...so the reclaim of refrigerant or vacuuming process can be done properly 0 default binary 1 default Deactivated 1 binary 2 Activated To stop the refrigerant recovery vacuuming mode push BS1 in case of...

Page 35: ...is setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table binary 1 30 1 default binary 2 default 40 2 binary 4 50 3 55 2 32 Forced a...

Page 36: ...pplicable legislation Power supply voltage Check the power supply voltage on the local supply panel The voltage MUST correspond to the voltage on the nameplate of the unit Earth wiring Be sure that th...

Page 37: ...mode 1 or 2 430 Push BS4 for 5 seconds or more The unit will start test operation Result The test operation is automatically carried out the compressor unit H2P flashes and the indication Test operati...

Page 38: ...it 19 Troubleshooting 19 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the abno...

Page 39: ...ction open circuit short circuit Compressor unit BIPH A1P X17A Check connection on PCB or actuator Low pressure sensor malfunction open circuit short circuit Compressor unit BIPL A1P X18A Check connec...

Page 40: ...sion valve malfunction subcool Compressor unit Y1E A1P X21A Check connection on PCB or actuator Electronic expansion valve malfunction main Heat exchanger unit Y1E A1P X7A Check connection on PCB or a...

Page 41: ...g to Q1 Q2 or indoor outdoor Check Q1 Q2 wiring Do NOT use Q1 Q2 Faulty wiring to Q1 Q2 or indoor outdoor Check Q1 Q2 wiring Do NOT use Q1 Q2 System test run abnormal ending Execute test run again War...

Page 42: ...3E R2T M1C R3T R7T R4T Y1S S1NPL S1PH S1NPH R5T f f l c b f g a d f m h f i j k e B A 3D110524 1 A Heat exchanger unit B Compressor unit a Stop valve gas circuit 2 to indoor units b Stop valve liquid...

Page 43: ...umulator R4T Thermistor subcool heat exchanger gas R5T Thermistor suction compressor R7T Thermistor liquid R10T Thermistor fin S1NPL Low pressure sensor S1NPH High pressure sensor S1PH High pressure s...

Page 44: ...e module A3P X37A Connector power supply for option PCB optional X66A Connector cool heat selector switch optional X1M Terminal strip power supply X A PCB connector X M Terminal strip on PCB A P X Y C...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...4P499900 1B 2021 12 Copyright 2017 Daikin 4P499900 1 B 00000002 Verantwortung f r Energie und Umwelt...

Reviews: