background image

8 Troubleshooting

Installation and operation manual

13

RK RKXYQ8T7Y1B
VRV IV compressor unit for indoor installation
4P499900-1B – 2021.12

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do  NOT  modify,  disassemble,  remove,  reinstall  or

repair  the  unit  yourself  as  incorrect  dismantling  or
installation  may  cause  an  electrical  shock  or  fire.
Contact your dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustion  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  ALWAYS  have  qualified
service personnel confirm that the point of leakage has
been repaired or corrected before resuming operation.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  OFF  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause  breakage,  electrical  shock  or  fire.  Contact  your
dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.

Turn OFF the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does NOT work
well.

Turn OFF the power
supply.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

Malfunction

Measure

If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.

▪ Check  if  air  inlet  or  outlet  of  heat

exchanger  unit  or  indoor  unit  is  not
blocked  by  obstacles.  Remove  any
obstacles and make sure the air can flow
freely.

▪ Check if the user interface display shows

 (time to clean the air filter). (Refer to

"7  Maintenance  and  service"

  [

4

  12]  and

"Maintenance" in the indoor unit manual.)

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  heat

exchanger  unit  or  indoor  unit  is  not
blocked  by  obstacles.  Remove  any
obstacle and make it well-ventilated.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

8.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

Main code

Contents

External protection device was activated

EEPROM failure (indoor)

Drain system malfunction (indoor)

Fan motor malfunction (indoor)

Swing flap motor malfunction (indoor)

Expansion valve malfunction (indoor)

Drain malfunction (indoor unit)

Filter dust chamber malfunction (indoor)

Capacity setting malfunction (indoor)

Transmission malfunction between main PCB and sub
PCB (indoor)

Heat exchanger thermistor malfunction (indoor; liquid)

Heat exchanger thermistor malfunction (indoor; gas)

Suction air thermistor malfunction (indoor)

Discharge air thermistor malfunction (indoor)

Summary of Contents for VRV IV i Series

Page 1: ...Installation and operation manual VRV IV compressor unit for indoor installation English Installation and operation manual VRV IV compressor unit for indoor installation RKXYQ5T8Y1B RKXYQ8T7Y1B...

Page 2: ...z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus nor...

Page 3: ...d senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t...

Page 4: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 5: ...door unit fan does not spin 15 8 2 15 Symptom The display shows 88 15 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 15 8 2 17 Symptom The inside of an...

Page 6: ...nstaller and user reference guide Preparation of the installation reference data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on http...

Page 7: ...rter A phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make...

Page 8: ...unsorted household waste If a chemical symbol is printed beneath the symbol this chemical symbol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols a...

Page 9: ...er such circumstances may cause breakage electrical shock or fire Contact your dealer WARNING The refrigerant in the system is safe and normally does NOT leak If the refrigerant leaks in the room cont...

Page 10: ...fter the heating operation stops The air flow rate may adjust itself depending on the room temperature or the fan may stop immediately This is not a malfunction 6 2 3 About the heating operation It ma...

Page 11: ...only for double flow multi flow corner ceiling suspended and wall mounted Refer to 6 4 Adjusting the air flow direction 411 for details To stop 4 Press the ON OFF button on the user interface once aga...

Page 12: ...nsert fingers rods or other objects into the air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injury CAUTION After a long use check the unit stand a...

Page 13: ...or breaker is activated Change the fuse or reset the breaker if necessary Malfunction Measure If the system goes into fan only operation but as soon as it goes into heating or cooling operation the sy...

Page 14: ...on centralised control device indoor unit Auto address malfunction inconsistency Auto address malfunction inconsistency 8 2 Symptoms that are NOT system malfunctions The following symptoms are NOT sys...

Page 15: ...is the sound of refrigerant gas flowing through both indoor and outdoor units A hissing sound which is heard at the start or immediately after stopping operation or defrost operation This is the noise...

Page 16: ...quid 9 5 mm 9 5 mm e Piping adapter 19 1 22 2 mm that you need when connecting piping to the heat exchanger unit only for 8 HP 11 1 2 To remove the transportation stay Only for RKXYQ5 NOTICE If the un...

Page 17: ...s for the compressor unit and heat exchanger unit For more possible options see the installer and user reference guide Cool heat selector In order to control the cooling or heating operation from a ce...

Page 18: ...SK OF BURNING SCALDING DANGER RISK OF ELECTROCUTION 1 Remove the service cover of the compressor unit 5 5 5 HP 8 HP 2 If you want to make field settings remove the inspection cover 5 HP 8 HP 3 If you...

Page 19: ...ameters mm sizes taken the following into account Select the pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refr...

Page 20: ...unit b Compressor unit c Refrigerant branch kit VRV DX VRV DX indoor unit EKEXV Expansion valve kit AHU Air handling unit H1 H5 Height differences L1 L7 Piping lengths Minimum and maximum piping leng...

Page 21: ...B C C C D D RDXYQ RDXYQ c c d d b b a a 5 HP 8 HP Method 2 First connect to the first 2 service ports C C b B a A Then connect to the last 2 service ports d B c A C C a b c d Service ports of stop va...

Page 22: ...cause malfunctions smoke or fire 14 3 Checking the refrigerant piping 14 3 1 About checking the refrigerant piping Refrigerant piping works are finished The indoor units compressor unit and or heat ex...

Page 23: ...e splitters to both circuits and check Without refrigerant line splitters takes twice as long You have to check the circuits separately To do so First connect the manifold to circuit 1 and check Then...

Page 24: ...ing according to the installation environment Ambient temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm If there is a possibility that condensation on the stop valve might...

Page 25: ...C C d B c A a Liquid line stop valve circuit 1 to heat exchanger unit b Gas line stop valve circuit 1 to heat exchanger unit c Gas line stop valve circuit 2 to indoor units d Liquid line stop valve ci...

Page 26: ...unction code and take corresponding action 19 1 Solving problems based on error codes 438 14 4 5 To fix the fluorinated greenhouse gases label 1 Fill in the label as follows b Contains fluorinated gre...

Page 27: ...tween the compressor unit the heat exchanger unit and the indoor units Example g f F1 F2 16 V F1 F2 16 V 220 240 V 1 50 Hz e c a d b 220 240 V 1 50 Hz 380 415 V 3N 50 Hz a Main switch b Earth connecti...

Page 28: ...he left side of the switch box 1 c 50 mm a b b X1M L1 F1F2 L2 L3 N c a c X2M A1P b a X1M X2M 5 HP 50 mm a b b a X1M X1M A1P X1M b a c c 8 HP X1M A1P c a Transmission wiring b Power supply c Cable tie...

Page 29: ...ing components See 13 2 1 To open the compressor unit 418 16 1 3 Field setting components The components to make field settings differ depending on the model Model Field setting components 5 HP Push b...

Page 30: ...ot displayed after 10 12 minutes check the malfunction code on the indoor unit user interface and in case of 8 HP on the compressor unit 7 segment display Solve the malfunction code accordingly First...

Page 31: ...HP You can change the value of setting 2 8 Te target temperature during cooling operation to 4 8 C as follows Action Button display 1 Start from the default situation 2 Select mode 2 BS1 5 s 3 Select...

Page 32: ...1 16 Shows the 3rd last malfunction code 7 segments display Mode 1 in case of 8 HP You can read out the following information Setting Value Description 1 1 Shows the status of low noise operation 0 Un...

Page 33: ...ay and the settings differ depending on the model Model Display Setting value 5 HP 7 LEDs display The seven LEDs give a binary representation of the setting value number 8 HP 7 segments display The th...

Page 34: ...so the reclaim of refrigerant or vacuuming process can be done properly 0 default binary 1 default Deactivated 1 binary 2 Activated To stop the refrigerant recovery vacuuming mode push BS1 in case of...

Page 35: ...is setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table binary 1 30 1 default binary 2 default 40 2 binary 4 50 3 55 2 32 Forced a...

Page 36: ...pplicable legislation Power supply voltage Check the power supply voltage on the local supply panel The voltage MUST correspond to the voltage on the nameplate of the unit Earth wiring Be sure that th...

Page 37: ...mode 1 or 2 430 Push BS4 for 5 seconds or more The unit will start test operation Result The test operation is automatically carried out the compressor unit H2P flashes and the indication Test operati...

Page 38: ...it 19 Troubleshooting 19 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the abno...

Page 39: ...ction open circuit short circuit Compressor unit BIPH A1P X17A Check connection on PCB or actuator Low pressure sensor malfunction open circuit short circuit Compressor unit BIPL A1P X18A Check connec...

Page 40: ...sion valve malfunction subcool Compressor unit Y1E A1P X21A Check connection on PCB or actuator Electronic expansion valve malfunction main Heat exchanger unit Y1E A1P X7A Check connection on PCB or a...

Page 41: ...g to Q1 Q2 or indoor outdoor Check Q1 Q2 wiring Do NOT use Q1 Q2 Faulty wiring to Q1 Q2 or indoor outdoor Check Q1 Q2 wiring Do NOT use Q1 Q2 System test run abnormal ending Execute test run again War...

Page 42: ...3E R2T M1C R3T R7T R4T Y1S S1NPL S1PH S1NPH R5T f f l c b f g a d f m h f i j k e B A 3D110524 1 A Heat exchanger unit B Compressor unit a Stop valve gas circuit 2 to indoor units b Stop valve liquid...

Page 43: ...umulator R4T Thermistor subcool heat exchanger gas R5T Thermistor suction compressor R7T Thermistor liquid R10T Thermistor fin S1NPL Low pressure sensor S1NPH High pressure sensor S1PH High pressure s...

Page 44: ...e module A3P X37A Connector power supply for option PCB optional X66A Connector cool heat selector switch optional X1M Terminal strip power supply X A PCB connector X M Terminal strip on PCB A P X Y C...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...4P499900 1B 2021 12 Copyright 2017 Daikin 4P499900 1 B 00000002 Verantwortung f r Energie und Umwelt...

Reviews: