background image

10

REYQ-TATJA / TAYDA 

EDUS371704C-D

4.2  Indoor Units

Capacity Range

0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton

1.5 ton

2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, 

Standard

Capacity Index

5.8 7.5 9.5

12

15

18

20

24

30

36

42

48

54

60

72

96

Ceiling mounted cassette 

(Round flow with sensing) 

type

FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T —

VJU

VISTA™ 2 × 2 cassette unit

FXZQ 05TA 07TA 09TA 12TA 15TA 18TA —

4-way blow ceiling-

suspended type

FXUQ —

— 18P 24P 30P 36P —

One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P —

Slim ceiling mounted duct 

type

FXDQ — 07M 09M 12M — 18M — 24M —

MSP concealed ducted unit

FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA —

Ceiling mounted duct type 

(Middle and high static 

pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB —

Ceiling mounted duct type

FXMQ —

— 72M 96M

Ceiling suspended type

FXHQ —

— 12M —

— 24M — 36M —

Wall mounted type

FXAQ — 07P 09P 12P — 18P — 24P —

Floor standing type

FXLQ — 07M 09M 12M — 18M — 24M —

Concealed floor standing 

type

FXNQ — 07M 09M 12M — 18M — 24M —

Air handling unit

FXTQ

— 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA —

VJUA

— 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA —

VJUD

VJ 

: 1 phase, 208 / 230 V, 60 Hz

U(VJU) : Standard symbol

Summary of Contents for VRV IV REYQ72TATJA

Page 1: ...EDUS371704C D 202002 Engineering Data Heat Recovery 60 Hz Design Manual REYQ TATJA 208 230 V REYQ TAYDA 460 V...

Page 2: ......

Page 3: ...lity 16 8 Capacity Range 17 8 1 Connection Ratio 17 8 2 Capacity Range of Connectable Indoor Units 18 8 3 Limitation of Capacity Index for Heat Recovery 19 9 Specifications 20 10 Dimensions 32 11 Serv...

Page 4: ...um Concentration 92 25 Safety Devices Setting 94 25 1 FXFQ T 94 25 2 FXZQ TA 94 25 3 FXUQ P 94 25 4 FXEQ P 94 25 5 FXDQ M 95 25 6 FXSQ TA 95 25 7 FXMQ PB 95 25 8 FXMQ M 95 25 9 FXHQ M 96 25 10 FXAQ P...

Page 5: ...and 100 ft vertical separation between indoor units Large capacity single module units reduce electrical and piping connections Dependable operation in extreme ambient conditions down to 13 F in heat...

Page 6: ...JU REYQ192TAYDA REYQ192TAYDU REYQ216TATJA REYQ216TATJU REYQ216TAYDA REYQ216TAYDU REYQ240TATJA REYQ240TATJU REYQ240TAYDA REYQ240TAYDU REYQ264TATJA REYQ264TATJU REYQ264TAYDA REYQ264TAYDU REYQ288TATJA RE...

Page 7: ...T A A TJ Minor Revision Power Supply Symbol TJ 3 phase 208 230 V 60 Hz YD 3 phase 460 V 60 Hz Indicates Minor Change Category Indicates Major Design Category Capacity Indication in Cooling Refrigeran...

Page 8: ...Btu h 60 60 000 Btu h 12 12 000 Btu h 36 36 000 Btu h 72 72 000 Btu h 15 15 000 Btu h 42 42 000 Btu h 96 96 000 Btu h Refrigerant Q R410A Shape F Ceiling mounted cassette Round flow with sensing Z VI...

Page 9: ...unit BS T VJ Q 36 Single Branch Selector unit only necessary for Heat Recovery System Power supply symbol VJ 1 phase 208 230 V 60 Hz Indicates major design category Capacity indication of connectable...

Page 10: ...00 Btu h 72 72 000 Btu h 96 96 000 Btu h Refrigerant Q R410A Shape M Ceiling mounted duct Series category X Inverter Unit category F Indoor unit for air cooled type Outdoor Air Processing Unit U G 300...

Page 11: ...360TATJA REYQ384TATJA REYQ408TATJA Outdoor unit 1 REYQ144TATJA REYQ168TATJA REYQ120TATJA REYQ96TATJA REYQ96TATJA Outdoor unit 2 REYQ168TATJA REYQ168TATJA REYQ120TATJA REYQ120TATJA REYQ144TATJA Outdoor...

Page 12: ...type FXEQ 07P 09P 12P 15P 18P 24P Slim ceiling mounted duct type FXDQ 07M 09M 12M 18M 24M MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA 24TA 30TA 36TA 48TA 54TA Ceiling mounted duct ty...

Page 13: ...Series Model Name Power Supply Standard Heat Recovery BS 4Q54T 6Q54T 8Q54T 10Q54T 12Q54T VJ Note No interchangeability between BSV Q36PVJU and BS Q54TVJ VJ 1 phase 208 230 V 60 Hz 4 4 Air Treatment E...

Page 14: ...4TATJA REYQ168TATJA Double Outdoor Units 16 ton 18 20 22 24 26 28 ton REYQ192TAYDA REYQ192TATJA REYQ216TAYDA REYQ240TAYDA REYQ264TAYDA REYQ288TAYDA REYQ312TAYDA REYQ336TAYDA REYQ216TATJA REYQ240TATJA...

Page 15: ...own with BYFQ60C3W1W Shown with BYFQ60C3W1S Ceiling suspended type FXHQ M 4 way blow ceiling suspended type FXUQ P Wall mounted type FXAQ P One way blow cassette type FXEQ P Floor standing type FXLQ M...

Page 16: ...A EDUS371704C D 5 3 Branch Selector Unit Single branch selector unit BSQ T Multi branch selector unit BS Q54T 5 4 Air Treatment Equipment Outdoor air processing unit FXMQ MF Energy recovery ventilator...

Page 17: ...6 3 2 BHFP26P100U BHFP26P100UA REYQ216TATJA REYQ216TAYDA 18 22 5 63 3 2 REYQ240TATJA REYQ240TAYDA 20 25 0 70 3 2 REYQ264TATJA REYQ264TAYDA 22 27 5 77 4 2 REYQ288TATJA REYQ288TAYDA 24 30 0 84 4 2 REYQ3...

Page 18: ...nit Multi Branch Selector unit Single Branch Selector unit Multi Branch Selector unit BSQ36TVJ BSQ60TVJ BSQ96TVJ BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS12Q54TVJ BSVQ36PVJU BSVQ60PVJU BSVQ96PVJU BS...

Page 19: ...130 1 In heating mode fan speed is limited to L tap when indoor units capacity 130 2 Fan speed follows a setting of the remote controller not limited by indoor units connection capacity 3 Fan speed i...

Page 20: ...6TATJA REYQ216TAYDA 108 to 280 345 37 20 240 REYQ240TATJA REYQ240TAYDA 120 to 312 384 41 22 264 REYQ264TATJA REYQ264TAYDA 132 to 343 422 45 24 288 REYQ288TATJA REYQ288TAYDA 144 to 374 460 49 26 312 RE...

Page 21: ...290 or less 290 or less 290 or less Maximum capacity index of connectable indoor units per branch 1 54 or less 54 or less 54 or less 54 or less 54 or less Note 1 When the total capacity of indoor uni...

Page 22: ...12 7 C1220T Brazing Connection Suction gas pipe in mm 3 4 19 1 C1220T Brazing Connection 7 8 22 2 C1220T Brazing Connection 1 1 8 28 6 C1220T Brazing Connection High Low pressure gas pipe in mm 5 8 1...

Page 23: ...C1220T Brazing Connection 5 8 15 9 C1220T Brazing Connection 5 8 15 9 C1220T Brazing Connection Suction gas pipe in mm 1 1 8 28 6 C1220T Brazing Connection 1 1 8 28 6 C1220T Brazing Connection 1 1 8 2...

Page 24: ...Direct Drive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 5 8 15 9 C1220T Brazing Connection 5 8 15 9 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in m...

Page 25: ...ive Direct Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in mm 1 3 8 34 9 C1220T Br...

Page 26: ...286 178 178 178 5 827 6 286 8 228 165 178 233 5 827 8 228 8 228 165 233 233 Drive Direct Drive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1...

Page 27: ...233 233 8 228 8 228 8 228 233 233 233 Drive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in mm 1...

Page 28: ...zing Connection Suction gas pipe in mm 3 4 19 1 C1220T Brazing Connection 7 8 22 2 C1220T Brazing Connection 1 1 8 28 6 C1220T Brazing Connection High Low pressure gas pipe in mm 5 8 15 9 C1220T Brazi...

Page 29: ...Brazing Connection 5 8 15 9 C1220T Brazing Connection 5 8 15 9 C1220T Brazing Connection Suction gas pipe in mm 1 1 8 28 6 C1220T Brazing Connection 1 1 8 28 6 C1220T Brazing Connection 1 1 8 28 6 C1...

Page 30: ...rive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 5 8 15 9 C1220T Brazing Connection 5 8 15 9 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in mm 1 1 8...

Page 31: ...rect Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in mm 1 3 8 34 9 C1220T Brazing...

Page 32: ...178 178 5 827 6 286 8 228 165 178 233 5 827 8 228 8 228 165 233 233 Drive Direct Drive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T...

Page 33: ...233 8 228 8 228 8 228 233 233 233 Drive Direct Drive Direct Drive Connecting pipes Liquid pipe in mm 3 4 19 1 C1220T Brazing Connection 3 4 19 1 C1220T Brazing Connection Suction gas pipe in mm 1 5 8...

Page 34: ...32 REYQ TATJA TAYDA EDUS371704C D 10 Dimensions REYQ72TATJA TAYDA 3D090838C...

Page 35: ...33 REYQ TATJA TAYDA EDUS371704C D REYQ96 168TATJA TAYDA C 3D090839C REYQ96 120TATJA TAYDA REYQ144 168TATJA TAYDA...

Page 36: ...ded then h2 2 and h1 2 should be added to the front and suction side service spaces respectively as shown in the following figure 3 When installing the units the most appropriate pattern should be sel...

Page 37: ...talling the units the most appropriate pattern should be selected from Installation and repair space drawing in order to obtain the best fit in the space available always bearing in mind the need to l...

Page 38: ...he most appropriate pattern should be selected from Installation and repair space drawing in order to obtain the best fit in the space available always bearing in mind the need to leave enough room fo...

Page 39: ...or unit side 2 If the above wall heights are exceeded then h2 2 and h1 2 should be added to the front and suction side service spaces respectively as shown in the following figure 3 When installing th...

Page 40: ...e above wall heights are exceeded then h2 2 and h1 2 should be added to the front and suction side service spaces respectively as shown in the following figure 3 When installing the units the most app...

Page 41: ...39 REYQ TATJA TAYDA EDUS371704C D 12 Center of Gravity REYQ72TATJA 4D090825A...

Page 42: ...40 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA 4D090826A...

Page 43: ...41 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA 4D090827A...

Page 44: ...42 REYQ TATJA TAYDA EDUS371704C D REYQ72TAYDA 4D090828A...

Page 45: ...43 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TAYDA 4D090829A...

Page 46: ...44 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TAYDA 4D090830A...

Page 47: ...The surface shall be finished with mortar The corner edges shall be chamfered 3 When the foundation is built on a concrete floor rubble is not necessary However the surface of the section on which th...

Page 48: ...46 REYQ TATJA TAYDA EDUS371704C D 14 Piping Diagrams REYQ72TATJA TAYDA 3D091128B...

Page 49: ...47 REYQ TATJA TAYDA EDUS371704C D REYQ96 168TATJA TAYDA 3D091127B...

Page 50: ...ADAPTOR REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER...

Page 51: ...IC RELAY Y3S A1P X1M TERMINAL BLOCK CONTROL A1P K11R MAGNETIC RELAY Y2S A1P X1M TERMINAL BLOCK ABC I P A9P K12R MAGNETIC RELAY Y4S A1P Y1E ELECTRONIC EXPANSION VALVE HEAT EXC UPPER K13R MAGNETIC RELAY...

Page 52: ...THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE INSTALLATI...

Page 53: ...OCK CONTROL A1P K7R K8R MAGNETIC RELAY E1HC E4HC A1P X1M TERMINAL BLOCK ABC I P A9P K9R MAGNETIC RELAY Y4S A1P Y1E ELECTRONIC EXPANSION VALVE HEAT EXC UPPER K11R MAGNETIC RELAY Y3S A1P Y2E ELECTRONIC...

Page 54: ...EFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE IN...

Page 55: ...R K8R MAGNETIC RELAY E1HC E4HC A1P X1M TERMINAL BLOCK CONTROL A1P K9R MAGNETIC RELAY Y4S A1P X1M TERMINAL BLOCK ABC I P A9P K11R MAGNETIC RELAY Y3S A1P Y1E ELECTRONIC EXPANSION VALVE HEAT EXC UPPER K1...

Page 56: ...REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE I...

Page 57: ...1M TERMINAL BLOCK POWER SUPPLY K3R MAGNETIC RELAY Y1S A1P X1M TERMINAL BLOCK CONTROL A1P K6R MAGNETIC RELAY OPTION A1P X1M TERMINAL BLOCK ABC I P A9P K7R MAGNETIC RELAY E1HC E2HC A1P Y1E ELECTRONIC EX...

Page 58: ...R TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE INSTA...

Page 59: ...7R MAGNETIC RELAY E1HC E2HC A1P X1M TERMINAL BLOCK CONTROL A1P K8R MAGNETIC RELAY E3HC E4HC A1P X1M TERMINAL BLOCK ABC I P A9P K9R MAGNETIC RELAY Y4S A1P Y1E ELECTRONIC EXPANSION VALVE HEAT EXC UPPER...

Page 60: ...EFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR 4 FOR CONNECTION WIRING TO INDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR OUTDOOR TRANSMISSION F1 F2 OUTDOOR MULTI TRANSMISSION Q1 Q2 REFER TO THE IN...

Page 61: ...AGNETIC RELAY Y1S A1P X13A X16A CONNECTOR E1HC E4HC K4R MAGNETIC RELAY Y2S A1P X1M TERMINAL BLOCK POWER SUPPLY K6R MAGNETIC RELAY OPTION A1P X1M TERMINAL BLOCK CONTROL A1P K7R MAGNETIC RELAY E1HC E2HC...

Page 62: ...Wiring shown are general points of connection guides only and are not intended for or to include all details for a specific installation 7 Be sure to install the switch and the fuse breaker to the po...

Page 63: ...shown are general points of connection guides only and are not intended for or to include all details for a specific installation 7 Be sure to install the switch and the fuse breaker to the power line...

Page 64: ...shown are general points of connection guides only and are not intended for or to include all details for a specific installation 7 Be sure to install the switch and the fuse breaker to the power line...

Page 65: ...36TATJA REYQ168TATJA 60 208 230 187 253 61 9 61 9 70 70 17 4 24 4 2 0 65 2 2 2 4 2 2 REYQ168TATJA REYQ360TATJA REYQ120TATJA 60 208 230 187 253 43 0 43 0 43 0 50 50 50 15 0 15 0 3 0 35 2 3 1 3 2 3 REYQ...

Page 66: ...416 508 36 1 36 1 40 40 7 9 11 1 2 0 6 2 2 1 0 2 2 REYQ168TAYDA REYQ360TAYDA REYQ120TAYDA 60 460 416 508 21 1 21 1 21 1 25 25 25 6 8 6 8 3 0 6 2 3 1 0 2 3 REYQ120TAYDA REYQ120TAYDA REYQ384TAYDA REYQ9...

Page 67: ...65 REYQ TATJA TAYDA EDUS371704C D 18 Operation Limits REYQ72 456TATJA TAYDA 3D091329A...

Page 68: ...but all indoor units connected to a multi branch selector box will operate as standard without the low ambient cooling function Function is engaged by a field setting on the outdoor unit to enable Low...

Page 69: ...67 REYQ TATJA TAYDA EDUS371704C D 20 Sound Levels Reference Data REYQ72TATJA TAYDA C 4D093380A...

Page 70: ...68 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA TAYDA C 4D093379A...

Page 71: ...69 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA TAYDA C 4D093378A...

Page 72: ...M33H9 KHRP25M33HA Max 8 branch KHRP25M33H9 KHRP25M33HA KHRP25M72H9 KHRP25M72HA Max 8 branch KHRP25M33H9 KHRP25M33HA KHRP25M72H9 KHRP25M72HA KHRP25M73HU9 KHRP25M73HUA REFNET joint KHRP25A22T9 KHRP25A22...

Page 73: ...f the peak load of each room Define required total heat load to outdoor unit Indoor unit capacity corrected for indoor air temperature WB Required heat load Safety factor for the indoor units Yes No P...

Page 74: ...3 7 157 1 14 00 30 7 32 2 16 8 16 8 24 9 23 4 14 2 14 2 173 2 16 00 36 1 36 4 13 3 13 3 21 5 21 2 13 0 13 0 167 8 Total heat load MBH From the above heat load calculation the maximum heat load for the...

Page 75: ...otal capacity MBH SHC Sensible heat capacity MBH Selection results of indoor units Room A Room B Room C Room D Room E Room F Room G Room H Max heat load MBH 36 1 36 4 17 3 17 3 30 9 30 8 14 2 14 2 Sel...

Page 76: ...6TAYDA 48 to 124 192 16 10 120 REYQ120TATJA REYQ120TAYDA 60 to 156 240 20 12 144 REYQ144TATJA REYQ144TAYDA 72 to 187 288 25 14 168 REYQ168TATJA REYQ168TAYDA 84 to 218 336 29 Double outdoor units 16 19...

Page 77: ...146 13 9 154 16 6 154 16 7 155 16 7 155 16 7 155 16 7 155 16 7 118 133 14 1 134 14 1 134 14 1 134 14 1 135 14 2 135 14 2 135 14 2 122 107 10 7 107 10 7 107 10 7 108 10 7 108 10 7 108 10 8 108 10 8 120...

Page 78: ...defrost correction factor for heating capacity Therefore C 201 8 0 924 1 161 160 6 MBH If the corrected capacity C is the same or greater than the required total heat load A selection is complete If C...

Page 79: ...77 REYQ TATJA TAYDA EDUS371704C D 23 Caution Label 23 1 REYQ72TATJA TAYDA Operation Name Plate 2P385982 1A...

Page 80: ...78 REYQ TATJA TAYDA EDUS371704C D 2P385982 1A...

Page 81: ...79 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385986 1A...

Page 82: ...80 REYQ TATJA TAYDA EDUS371704C D 3P385986 1A...

Page 83: ...81 REYQ TATJA TAYDA EDUS371704C D 23 2 REYQ96 168TATJA TAYDA Operation Name Plate 3P385983 1B...

Page 84: ...82 REYQ TATJA TAYDA EDUS371704C D 3P385983 1B...

Page 85: ...83 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 86: ...84 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 87: ...85 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 88: ...86 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 89: ...87 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 90: ...88 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...

Page 91: ...89 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385987 1A...

Page 92: ...90 REYQ TATJA TAYDA EDUS371704C D 3P385987 1A...

Page 93: ...f refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum cha...

Page 94: ...lity is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged Step 2 Calculate the smallest room volume ft 3 In case lik...

Page 95: ...d If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maxim...

Page 96: ...board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Fan motor thermal fuse F C Fan motor thermal protector F C Drain pump fuse F C C 4D110603 25 3 FXUQ P Model FX...

Page 97: ...15 A Printed circuit board fuse Fan driver 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A 250 V 6 3 A Drain pump thermal fuse F C 3D112398 25 7 FXMQ PB Model FXMQ07PBVJU FXMQ09PBVJU FXMQ...

Page 98: ...248 120 or less OFF 275 18 135 10 ON 248 120 or less OFF 275 18 135 10 ON 248 120 or less OFF 275 18 135 10 ON 248 120 or less OFF 275 18 135 10 ON 248 120 or less C 3D045646B 25 12 FXTQ TA Model FXT...

Page 99: ...97 REYQ TATJA TAYDA EDUS371704C D Appendix 1 Introduction 98 1 1 ED Book List 98 1 2 Publication List of Engineering Data for VRV Products 99...

Page 100: ...ssette Type FXEQ P EDUS391533 F16 Slim Ceiling Mounted Duct Type FXDQ M EDUS39 600 F2 MSP Concealed Duct Unit FXSQ TA EDUS391777 F17 Ceiling Mounted Duct Type FXMQ PB EDUS391503A F4 Ceiling Mounted Du...

Page 101: ...da Design manual EDUS371706C D Capacity table EDUS371706C C H P 208 230 V 460 V RXYQ TATJA TAYDA USA Canada Design manual EDUS341703B D Jan 2020 Capacity table EDUS341703B C 575 V RXYQ TAYCA Canada De...

Page 102: ...F5 Sep 2006 Wall Mounted Type FXAQ07 24PVJU USA EDUS391100 F6 Jan 2012 Floor Standing Type Concealed Floor Standing Type FXLQ07 24MVJU FXNQ07 24MVJU USA EDUS391502 F7 Jul 2015 Air Handling Unit FXTQ0...

Page 103: ......

Page 104: ...r explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessorie...

Reviews: