22. Selection Procedure
22.1 Selection Procedure
22.1.1 Flowchart
Provisionally select outdoor unit type and size based on limitation of connection ratio
Correct for cooling & heating capacity of the outdoor unit by the following items
VRV
system selection is complete.
Confirm that the number of indoor units connected to the outdoor unit is within limitation.
Corrected capacity of the outdoor unit
≥
Required total heat load to the outdoor unit
2) Use the system peak load
1) Use the sum of the peak load of each room
Define required total heat load to outdoor unit
Indoor unit capacity corrected for indoor air temperature (WB)
≥
Required heat load × Safety factor for the indoor units
Yes
No
-Piping length, level difference
-Piping heat loss
-Safety factor for the outdoor unit
-Defrost (only for heating capacity)
-Outdoor air temperature
-Indoor air temperature
-Connection ratio
Given Conditions:
· Design temperature and humidity (indoor & outdoor)
· Required heat load of each room
· System peak load (if necessary)
· Piping length, level difference
· Specifications of indoor units (type and number)
Define safety factor for the indoor units and outdoor unit
[1] Given conditions
[2] Selection of indoor units
[3] Selection of outdoor unit
Summary of Contents for VRV IV REYQ72TATJA
Page 2: ......
Page 34: ...32 REYQ TATJA TAYDA EDUS371704C D 10 Dimensions REYQ72TATJA TAYDA 3D090838C...
Page 41: ...39 REYQ TATJA TAYDA EDUS371704C D 12 Center of Gravity REYQ72TATJA 4D090825A...
Page 42: ...40 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA 4D090826A...
Page 43: ...41 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA 4D090827A...
Page 44: ...42 REYQ TATJA TAYDA EDUS371704C D REYQ72TAYDA 4D090828A...
Page 45: ...43 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TAYDA 4D090829A...
Page 46: ...44 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TAYDA 4D090830A...
Page 48: ...46 REYQ TATJA TAYDA EDUS371704C D 14 Piping Diagrams REYQ72TATJA TAYDA 3D091128B...
Page 49: ...47 REYQ TATJA TAYDA EDUS371704C D REYQ96 168TATJA TAYDA 3D091127B...
Page 67: ...65 REYQ TATJA TAYDA EDUS371704C D 18 Operation Limits REYQ72 456TATJA TAYDA 3D091329A...
Page 69: ...67 REYQ TATJA TAYDA EDUS371704C D 20 Sound Levels Reference Data REYQ72TATJA TAYDA C 4D093380A...
Page 70: ...68 REYQ TATJA TAYDA EDUS371704C D REYQ96 120TATJA TAYDA C 4D093379A...
Page 71: ...69 REYQ TATJA TAYDA EDUS371704C D REYQ144 168TATJA TAYDA C 4D093378A...
Page 80: ...78 REYQ TATJA TAYDA EDUS371704C D 2P385982 1A...
Page 81: ...79 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385986 1A...
Page 82: ...80 REYQ TATJA TAYDA EDUS371704C D 3P385986 1A...
Page 83: ...81 REYQ TATJA TAYDA EDUS371704C D 23 2 REYQ96 168TATJA TAYDA Operation Name Plate 3P385983 1B...
Page 84: ...82 REYQ TATJA TAYDA EDUS371704C D 3P385983 1B...
Page 85: ...83 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 86: ...84 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 87: ...85 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 88: ...86 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 89: ...87 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 90: ...88 REYQ TATJA TAYDA EDUS371704C D 1P385984 1A...
Page 91: ...89 REYQ TATJA TAYDA EDUS371704C D Collective Indications Label 3P385987 1A...
Page 92: ...90 REYQ TATJA TAYDA EDUS371704C D 3P385987 1A...
Page 103: ......