16 Configuration
Installation and operation manual
33
RK RKXYQ8T7Y1B
VRV IV compressor unit for indoor installation
4P499900-1A – 2020.10
Setting
Value / Description
[1‑1]
Shows the status
of low noise
operation.
0
Unit is currently not operating under low
noise restrictions.
1
Unit is currently operating under low
noise restrictions.
Low noise operation reduces the sound
generated by the unit compared to nominal
operating conditions.
Low noise operation can be set in mode 2.
There are two methods to activate low noise
operation of the compressor unit and heat
exchanger unit.
▪ The first method is to enable an automatic low
noise operation during night time by field
setting. The unit will operate at the selected
low noise level during the selected time
frames.
▪ The second method is to enable low noise
operation based on an external input. For this
operation an optional accessory is required.
[1‑2]
Shows the status
of power
consumption
limitation
operation.
0
Unit is currently not operating under
power consumption limitations.
1
Unit is currently operating under power
consumption limitation.
Power consumption limitation reduces the power
consumption of the unit compared to nominal
operating conditions.
Power consumption limitation can be set in
mode 2. There are two methods to activate
power consumption limitation of the compressor
unit.
▪ The first method is to enable a forced power
consumption limitation by field setting. The
unit will always operate at the selected power
consumption limitation.
▪ The second method is to enable power
consumption limitation based on an external
input. For this operation an optional accessory
is required.
Setting
Value / Description
[1‑5]
Shows the current
T
e
target
parameter
position.
For more information, see setting [2‑8].
[1‑6]
Shows the current
T
c
target
parameter
position.
For more information, see setting [2‑9].
[1‑10]
Shows the total
number of
connected units
(heat exchanger
unit + indoor
units).
It can be convenient to check if the total number
of units which are installed (heat exchanger unit
+ indoor units) match the total number of units
which are recognised by the system. In case
there is a mismatch, it is advised to check the
communication wiring path between compressor
unit and heat exchanger unit, and between
compressor unit and indoor units (F1/F2
communication line).
[1‑17]
Shows the latest
malfunction code.
When the latest malfunction codes were reset by
accident on an indoor unit user interface, they
can be checked again through this monitoring
settings.
For the content or reason behind the malfunction
code see
"19.1 Solving problems based on error
38], where most relevant malfunction
codes are explained. Detailed information about
malfunction codes can be consulted in the
service manual of this unit.
[1‑18]
Shows the 2nd
last malfunction
code.
[1‑19]
Shows the 3rd
last malfunction
code.
[1‑40]
Shows the current
cooling comfort
setting.
For more information, see setting [2‑81].
[1‑41]
Shows the current
heating comfort
setting.
For more information, see setting [2‑82].
16.1.8
Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The display and the settings differ depending on the model.
Model
Display
Setting/value
5 HP
7‑LEDs display
The seven LEDs give a binary representation of the setting/value number.
8 HP
7‑segments display
The three 7‑segments show the setting/value number.
Setting
Value
(8 HP)
(5 HP)
Description
[2‑8]
T
e
target temperature during cooling operation.
0 (default)
(default)
Auto
2
6°C
3
7°C
4
8°C
5
9°C
6
10°C
7
11°C