5 Preparation

Installer and user reference guide

10

RXYTQ8~16U7YF

VRV IV+ heat pump for high ambient temperatures

4P561157-1 – 2018.09

Possible standard combinations of outdoor units

INFORMATION

U-series  units  cannot  share  the  same  refrigerant  circuit
with  T-series  units.  However,  electrically,  U-series  units
and T-series units can be connected via F1/F2.

▪ RXYTQ18~48 consist of 2 or 3 RXYTQ8~16 units.

▪ Only the combinations in the table below are allowed.

Continuous heating

RXYTQ18 = R 8

RXYTQ20 = R 10

RXYTQ22 = R 12

RXYTQ24 = R 12

RXYTQ26 = R 12

RXYTQ28 = R 14

RXYTQ30 = R 10 + 10

RXYTQ32 = R 10 + 10

RXYTQ34 = R 12 + 10

RXYTQ36 = R 12 + 12

RXYTQ38 = R 12 + 12

RXYTQ40 = R 14 + 12

RXYTQ42 = R 14 + 14

RXYTQ44 = R 16 + 12

RXYTQ46 = R 16 + 14

RXYTQ48 = R 16 + 16

4.5.4

Possible options for the outdoor unit

INFORMATION

Refer to the technical engineering data for the latest option
names.

Refrigerant branching kit

Description

Model name

Refnet header

KHRQ22M29H

KHRQ22M64H

KHRQ22M75H

Refnet joint

KHRQ22M20T

KHRQ22M29T9

KHRQ22M64T

KHRQ22M75T

For  the  selection  of  the  optimal  branching  kit,  please  refer  to

"5.3.3 To select refrigerant branch kits" on page 14

.

Outdoor multi connection piping kit

Number of outdoor units

Model name

2

BHFQ22P1007

3

BHFQ22P1517

Cool/heat selector

In  order  to  control  the  cooling  or  heating  operation  from  a  central
location, the following option can be connected:

Description

Model name

Cool/heat changeover switch

KRC19-26A

Cool/heat changeover PCB

BRP2A81

With optional fixing box for the
switch

KJB111A

External control adaptor (DTA104A61/62)

To  instruct  specific  operation  with  an  external  input  coming  from  a
central control the external control adaptor can be used. Instructions
(group  or  individual)  can  be  instructed  for  low  noise  operation  and
power consumption limitation operation.

PC configurator cable (EKPCCAB)

You  can  make  several  commissioning  field  settings  through  a
personal  computer  interface.  For  this  option  EKPCCAB  is  required
which  is  a  dedicated  cable  to  communicate  with  the  outdoor  unit.
The 

user 

interface 

software 

is 

available 

on 

http://

www.daikineurope.com/support-and-manuals/software-downloads/

.

Demand PCB (EKRP1AHTA)

To  enable  the  power  saving  consumption  control  by  digital  inputs
you must install the demand PCB.

For  installation  instructions,  see  the  installation  manual  of  the
demand PCB and addendum book for optional equipment.

5

Preparation

5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.

It contains information about:

▪ Preparing the installation site

▪ Preparing the refrigerant piping

▪ Preparing the electrical wiring

5.2

Preparing the installation site

5.2.1

Installation site requirements of the
outdoor unit

▪ Provide  sufficient  space  around  the  unit  for  servicing  and  air

circulation.

▪ Make  sure  the  installation  site  withstands  the  unit's  weight  and

vibration.

▪ Make  sure  the  area  is  well  ventilated.  Do  NOT  block  any

ventilation openings.

▪ Make sure the unit is level.

▪ Select a place where rain can be avoided as much as possible.

▪ Select  the  location  of  the  unit  in  such  a  way  that  the  sound

generated by the unit does not disturb anyone, and the location is
selected according the applicable legislation.

Do NOT install the unit in the following places:

▪ In potentially explosive atmospheres.

▪ In  places  where  there  is  machinery  that  emits  electromagnetic

waves.  Electromagnetic  waves  may  disturb  the  control  system,
and cause malfunction of the equipment.

▪ In  places  where  there  is  a  risk  of  fire  due  to  the  leakage  of

flammable  gases  (example:  thinner  or  gasoline),  carbon  fibre,
ignitable dust.

▪ In  places  where  corrosive  gas  (example:  sulphurous  acid  gas)  is

produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

Summary of Contents for VRV IV+ RXYTQ8U7YF

Page 1: ...ser reference guide VRV IV heat pump for high ambient temperatures English Installer and user reference guide VRV IV heat pump for high ambient temperatures RXYTQ8U7YF RXYTQ10U7YF RXYTQ12U7YF RXYTQ14U...

Page 2: ...ltiple outdoor units Knockout holes 20 6 4 7 To connect the refrigerant branching kit 20 6 4 8 To protect against contamination 20 6 4 9 To braze the pipe end 21 6 4 10 Using the stop valve and servic...

Page 3: ...9 19 2 2 Symptom Cool Heat cannot be changed over 59 19 2 3 Symptom Fan operation is possible but cooling and heating do not work 59 19 2 4 Symptom The fan speed does not correspond to the setting 59...

Page 4: ...emical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential...

Page 5: ...e consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate W...

Page 6: ...ll an earth leakage protector Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency ele...

Page 7: ...fter the box with the outdoor unit is delivered on site It contains information about Unpacking and handling the outdoor unit Removing the accessories from the unit Removing the transportation stay Ke...

Page 8: ...TH OF LIQUID PIPE SIZE O9 5 x 0 059 TOTAL LENGTH OF LIQUID PIPE SIZE O6 4 x 0 022 105 CR 130 50 CR 105 50 CR 70 70 CR 85 85 CR 105 105 CR 130 8HP Total indoor unit capacity connection ratio CR 10 12HP...

Page 9: ...ON Not all combinations of indoor units are allowed for guidance see 4 5 2 Possible combinations of indoor units on page 9 e d c c b f a a VRV IV Heat pump outdoor unit b Refrigerant piping c VRV dire...

Page 10: ...nfigurator cable EKPCCAB You can make several commissioning field settings through a personal computer interface For this option EKPCCAB is required which is a dedicated cable to communicate with the...

Page 11: ...oundings When installing the unit in a small room take measures in order to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak refer to About...

Page 12: ...d space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required According to the appropriate European Standard the maximum allowed concen...

Page 13: ...he piping length on page 14 5 3 2 To select the piping size Determine the proper size using the following tables and reference figure only for indication A B B B C D E x y b a 1 2 3 4 b 1 2 3 4 VRV DX...

Page 14: ...refnet joints other than the first branch example refnet joint b select the proper branch kit model based on the total capacity index of all indoor units connected after the refrigerant branch Indoor...

Page 15: ...000 m 500 m Example 1 1 a b c d e f g h i j k l m n p 1000 m Example 2 1 a b c d e f g h i j k l m n p 500 m Between outdoor branch and outdoor unit only in case 16 HP Actual piping length 10 m Exampl...

Page 16: ...g c When the piping size is increased step b the piping length has to be counted as double except for the main pipe and the pipes that are not increased in pipe size The total piping length has to be...

Page 17: ...safety devices required by the applicable legislation WARNING ALWAYS use multicore cable for power supply cables 5 4 2 Safety device requirements The power supply must be protected with the required...

Page 18: ...HP 6 SW8 NOTICE When closing the electrical component box cover make sure that the sealing material on the lower back side of the cover is NOT caught and bend towards the inside a b c d e a Electrica...

Page 19: ...gerant Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation Only use phosphoric acid deoxidised seamless copper NOTICE After all the piping has been connect...

Page 20: ...t the total length of the piping connected to the joint is absolute straight for more than 500 mm Only if a straight field piping of more than 120 mm is connected more than 500 mm of straight section...

Page 21: ...e pipe corrosion or in particular if the flux contains fluorine it will deteriorate the refrigerant oil 6 4 10 Using the stop valve and service port To handle the stop valve Make sure to keep all stop...

Page 22: ...he connection of the field piping in case the recovery was not complete 6 5 Checking the refrigerant piping 6 5 1 About checking the refrigerant piping Refrigerant piping works are finished The indoor...

Page 23: ...y is set to the unit If not see also the flow chart earlier described in this chapter see 6 5 1 About checking the refrigerant piping on page 22 6 5 4 To perform a leak test The leak test must satisfy...

Page 24: ...rigerant always use protective gloves and safety glasses NOTICE If the power of some units is turned off the charging procedure cannot be finished properly NOTICE In case of a multiple outdoor system...

Page 25: ...0 kg 1 kg 105 CR 130 0 5 kg 1 5 kg 30 m 50 CR 70 0 kg 1 kg 70 CR 85 0 3 kg 0 5 kg 1 5 kg 85 CR 105 0 7 kg 1 kg 2 kg 105 CR 130 1 2 kg 1 5 kg a In case of a multi outdoor unit system add the sum of the...

Page 26: ...re charging refrigerant Step 1 Calculate additional refrigerant charge amount R kg Refrigerant overcharge happened recover refrigerant to reach R Q Step 2 Open valves C and B to the liquid line Execut...

Page 27: ...ithout outdoor unit operation If Then The additional refrigerant amount is smaller than 10 kg Perform steps 2 3 The additional refrigerant charge is larger than 10 kg Perform steps 2 8 3 Pre charging...

Page 28: ...ns of the manual refrigerant charge operation mode 1 Take all the precautions mentioned in 7 Configuration on page 32 and 8 Commissioning on page 40 into account 2 Turn on the power of the indoor unit...

Page 29: ...nstalling the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector Install power...

Page 30: ...ssion Maximum wiring length 1000 m Total wiring length 2000 m Maximum inter unit wiring length between outdoor units 30 m Transmission wiring to cool heat selector 500 m Maximum number of branches 16...

Page 31: ...ansmission F1 F2 f Outdoor unit other system transmission F1 F2 INFORMATION U series units cannot share the same refrigerant circuit with T series units However electrically U series units and T serie...

Page 32: ...8 power terminal block 5 5 7 3 M8 ground NOTICE When connecting the earth wire align the wire with the cut out section of the cup washer Incomplete earthing may cause electrical shock The power supply...

Page 33: ...uttons 7 2 3 To access the field setting components It is not required to open the complete electronic component box to access the push buttons on the PCB and read out the 7 segment display s To acces...

Page 34: ...ttings of the outdoor unit and system What How Changing and accessing the setting in mode 2 Once mode 2 is selected push BS1 for more than 5 seconds you can select the wanted setting It is done by pus...

Page 35: ...ecognised by the system In case there is a mismatch it is recommended to check the communication wiring path between outdoor and indoor units F1 F2 communication line 1 13 Shows the total number of co...

Page 36: ...or vacuuming process can be done properly 2 21 Description 0 default Deactivated 1 Activated To stop the refrigerant recovery vacuuming mode push BS3 If BS3 is not pushed the system will remain in ref...

Page 37: ...able conditions The intentional target however is fixed and will be used to obtain the best balance between energy consumption and comfort depending on the application type 7 3 1 Available main operat...

Page 38: ...llowed to go down to 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to go up to 46 C on temporary base depending on the situation Whe...

Page 39: ...Te Evaporating temperature Quick Powerful Mild Room temperature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful 7 3 4 Example Automati...

Page 40: ...starting up the unit Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 6 8 Connecting the electrical wiring on page 29 according to...

Page 41: ...g start up control Cooling stable condition Communication check Stop valve check Pipe length check Refrigerant amount check Pump down operation Unit stop Note During the test operation it is not possi...

Page 42: ...Making field settings on page 33 for details how to set mode 2 When vacuuming recovery mode is used check very carefully what should be vacuumed recovered before starting See installation manual of t...

Page 43: ...top valve closed Refrigerant shortage Indoor unit malfunction Open stop valves Check refrigerant amount recharge unit Check the user interface s display or transmission wiring between the outdoor unit...

Page 44: ...PCB or actuator De icing temperature sensor malfunction R7T A1P X30A Check connection on PCB or actuator Liquid temperature sensor after subcool HE malfunction R5T A1P X30A Check connection on PCB or...

Page 45: ...Wrong type of indoor units combined R410A R407C RA Hydrobox etc Indoor unit malfunction Check if other indoor units have malfunction and confirm indoor unit mix is allowed Connection malfunction over...

Page 46: ...eration Retry when ambient conditions are satisfied Outdoor unit is out of temperature range for leak detection operation Retry when ambient conditions are satisfied Too low pressure was noticed durin...

Page 47: ...Layout A B C D A B Possibility 1 Possibility 2 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50...

Page 48: ...n Y1S p 4 way valve sub Y5S q Electrical component box r Service port refrigerant charge s Stop valve liquid t Stop valve gas u Expansion valve liquid cooling Y3E v Service port Piping diagram RXYTQ10...

Page 49: ...essor M1C b Compressor M2C c Heat exchanger d Fan e Fan motor M1F M2F f Accumulator g Expansion valve main Y1E h Expansion valve subcool heat exchanger Y2E i Expansion valve storage vessel Y4E j Subco...

Page 50: ...d circuit board noise filter A3P Printed circuit board inverter A4P Printed circuit board fan A5P Printed circuit board ABC I P option BS1 BS3 A1P Push button switch MODE SET RETURN C A3P Capacitor DS...

Page 51: ...R L2R Reactor M1C M2C Motor compressor M1F M2F Motor fan PS A1P A3P A6P Switching power supply Q1DI Earth leakage circuit breaker field supply Q1LD A1P Earth current detector field supply R24 A4P A7P...

Page 52: ...to perform this work CAUTION It is not good for your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with bur...

Page 53: ...eating operation the indoor fan is automatically stopped The display of the user interface shows It may take some time before the fan starts This is not a malfunction INFORMATION The heating capacity...

Page 54: ...tem stops operating NOTICE Do not turn off power immediately after the unit stops but wait for at least 5 minutes 16 4 Adjusting the air flow direction Refer to the operation manual of the user interf...

Page 55: ...filter ask a qualified service person to clean the filters Refer to Maintenance in the indoor unit manual Keep the indoor unit and user interface at least 1 m away from televisions radios stereos and...

Page 56: ...tains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE In Europe the greenhouse gas emissions of the total ref...

Page 57: ...ears Pressure containing parts In case of corrosion contact your local dealer NOTICE The table indicates main components Refer to your maintenance and inspection contract for more details The table in...

Page 58: ...tion air thermistor malfunction indoor Discharge air thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB mal...

Page 59: ...oor unit is extremely contaminated the temperature distribution inside a room becomes uneven It is necessary to clean the interior of the indoor unit Ask your dealer for details on cleaning the unit T...

Page 60: ...Units MUST be treated at a specialised treatment facility for reuse recycling and recovery 22 Glossary Dealer Sales distributor for the product Authorized installer Technical skilled person who is qu...

Page 61: ......

Page 62: ......

Page 63: ......

Page 64: ...4P561157 1 2018 09 Copyright 2018 Daikin...

Reviews: