Field Setting from Outdoor Unit
SiUS331604E
111
Field Setting
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
In setting mode 2, push the
BS1
(
MODE
button) one time.
→
The system enters setting mode 1 and the H1P
goes off.
In setting mode 1, the H6P (In low noise operation) and the H7P (In demand control) keep lighting.
2. Setting mode 2 (H1P on)
(1) In setting mode 1, push and hold the
BS1
(
MODE
button) for more than 5 seconds.
→
The system enters
setting mode 2 and the H1P lights up.
(2) Push the
BS2
(
SET
button) several times and match the LED display with the Setting No. you want.
(3) Push the
BS3
(
RETURN
button) one time, and the present setting content is displayed.
→
Push the
BS2
(
SET
button) several times and match the LED display with the setting content (as shown on
next page) you want.
(4) Push the
BS3
(
RETURN
button) two times.
→
The system returns to (1).
(5) Push the
BS1
(
MODE
button) one time.
→
The system returns to setting mode 1 and the H1P goes off.
{
: ON
z
: OFF
l
: Blink
(1)
(2)
(3)
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
demand
setting
{
z
z
z
z
z
z
{
z
z
{
{
z
z
NO
(Factory
setting)
{
z
z
z
z
z
l
YES
{
z
z
z
z
l
z
22
Night-time
low noise
setting
{
z
{
z
{
{
z
OFF
(Factory
setting)
{
z
z
z
z
z
z
Level 1
{
z
z
z
z
z
l
Level 2
{
z
z
z
z
l
z
Level 3
{
z
z
z
z
l
l
26
Night-time
low noise
operation
start setting
{
z
{
{
z
{
z
PM 8:00
{
z
z
z
z
z
l
PM 10:00
(Factory
setting)
{
z
z
z
z
l
z
PM 0:00
{
z
z
z
l
z
z
27
Night-time
low noise
operation
end setting
{
z
{
{
z
{
{
AM 6:00
{
z
z
z
z
z
l
AM 7:00
{
z
z
z
z
l
z
AM 8:00
(Factory
setting)
{
z
z
z
l
z
z
29
Capacity
precedence
setting
{
z
{
{
{
z
{
Low noise
precedence
(Factory
setting)
{
z
z
z
z
z
l
Capacity
precedence
{
z
z
z
z
l
z
30
Demand
setting 1
{
z
{
{
{
{
z
60 % of
rated power
consumption
{
z
z
z
z
z
l
70 % of
rated power
consumption
(Factory
setting)
{
z
z
z
z
l
z
80 % of
rated power
consumption
{
z
z
z
l
z
z
32
Constant
demand
setting
{
{
z
z
z
z
z
OFF
(Factory
setting)
{
z
z
z
z
z
l
ON
{
z
z
z
z
l
z
Setting mode indication section
Setting No. indication section
Set contents indication section
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...