Service Check Function
SiUS331604E
131
Service Diagnosis
3.4
Error Code Indication by Outdoor Unit PCB
Selection of setting item
Confirmation of error 1
To enter the monitor mode, press
the MODE (BS1) button when in
“Setting mode 1”.
Press the SET (BS2) button and set
the LED display to a setting item.
Press the RETURN (BS3) button
once to display "First digit" of error
code.
Confirmation of error 2
Press the SET (BS2) button once to
display "Second digit" of error code.
Press the RETURN (BS3) button
and switches to the initial status of
“Monitor mode”.
∗
Press the MODE (BS1) button and
returns to “Setting mode 1”.
Confirmation of error 3
Press the SET (BS2) button once to
display "error location".
Detailed
description
on next
page.
Confirmation of error 4
Press the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "error location".
Monitor mode
Contents of Error
Error Code
PCB abnormality
E1
Abnormal high pressure switch
High pressure switch activated
E3
Abnormal low pressure switch
Low pressure switch activated
E4
Compressor lock
Detection of INV. compressor lock
E5
Overload, overcurrent,
abnormal lock of outdoor unit fan motor
Detection of DC fan 1 motor lock
E7
Detection of DC fan 2 motor lock
Electronic expansion valve
abnormality
Main
E9
Subcooling
Abnormal discharge pipe temperature
Abnormal Tdi
F3
Abnormal heat exchanger temperature Refrigerant overcharge
F6
Defective thermistor of outdoor air
temperature
Defective Ta sensor (short)
H9
Defective discharge pipe thermistor
Defective Tdi sensor (short)
J3
Defective suction pipe thermistor
Defective Ts1 sensor (short)
J5
Defective Ts2 sensor (short)
Defective outdoor heat exchanger
deicer thermistor
Defective Tb sensor (short)
J6
Defective outdoor heat exchanger
liquid pipe thermistor
Defective TI sensor (short)
J7
Defective subcooling heat exchanger
gas pipe thermistor
Defective Tsh sensor (short)
J9
Defective sensor of high pressure
Defective Pc sensor (short)
JA
Defective sensor of low pressure
Defective Pe sensor (short)
JC
Defective PCB (for inverter
compressor)
Defective IPM
L1
Abnormal current sensor offset
Abnormal IGBT
Defective current sensor
Abnormal SP-PAM overvoltage
Abnormal Interleave
Abnormal inverter jumper setting
Abnormal EEPROM
Inverter radiation fin temperature rising Overheating of inverter radiation fin temperature
L4
DC output overcurrent
Inverter instantaneous overcurrent
L5
Electronic thermal
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)
Stall prevention (Current increasing)
L9
Stall prevention (Defective start up)
Abnormal wave form in startup
Out-of-step
Transmission error (Between microcomputers on the outdoor main PCB)
LC
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...