Troubleshooting by Error Code
SiUS331604E
135
Service Diagnosis
4. Troubleshooting by Error Code
4.1
External Protection Device Abnormality
Error Code
A0
Applicable
Models
All indoor units
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set for
external ON/OFF input.
Supposed
Causes
Activation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
ON/OFF
input from
outside (mode No.
12, first code No. 1) has
been set to external protection
device input (second
code No. 03) by
remote
controller.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the setting state of the
external ON/OFF input by
remote controller.
Ex
ternal
protection device
is connected to terminals
T1 and T2 of the indoor
unit terminal
block.
Replace the indoor unit main
PCB (A1P).
Actuation of external protection
device.
Change the second code No. to
01
or
02
.
YES
NO
NO
YES
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...