SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
138
Note:
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit main
PCB (A1P).
Replace the drain pump or
check for dirt, etc.
YES
YES
NO
NO
The drain
pump works when
the power supply is reset for
the indoor unit.
The
voltage of
drain pump
terminals (
∗
2) is 208-
230 V (within 5 minutes of
resetting the power
supply).
A
Model
∗
1: Float switch (S1L) / short
circuit connector
∗
2: Drain pump (M1P)
connector
Note
FXFQ-T
X15A
X10A
–
FXFQ-P
X15A
X25A
–
FXZQ
X8A
X25A
–
FXUQ
X15A
X25A
–
FXEQ
X15A
X25A
–
FXDQ
X8A
X25A
–
FXMQ-PB
X15A
X25A
–
FXMQ-M
X8A
–
Option
FXAQ
X15A
–
Option