SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
164
Troubleshooting
NO
YES
YES
NO
YES
YES
NO
NO
Diagnosis procedure 4
Infrared floor sensor error
(Error code
CE-04
)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to
sensor and address data No. 26.
Is the
connection of the adaptor
PCB connector X9A
normal? (
∗
)
Is the
connection of the
sensor connector
normal?
Displays
"--" by the above
verification
method.
Displays
CE-04
again or "--"
for sensor and address
data.
Replace the sensor.
∗
Check whether A2P connector is well connected or not.
Connect the connector correctly.
Connect the connector correctly.
Normal.
Normal.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...