Troubleshooting by Error Code
SiUS331604E
183
Service Diagnosis
4.31 Radiation Fin Temperature Rise Abnormality
Error Code
L4
Applicable
Models
All outdoor units
Method of Error
Detection
The radiation fin temperature is detected by the radiation fin thermistor.
Error Decision
Conditions
The radiation fin temperature exceeds a certain temperature.
Supposed
Causes
Activation of radiation fin thermistor
Defective outdoor main PCB
Defective radiation fin thermistor
Troubleshooting
Defective radiation from the power
unit
• Blocked air suction port
• Stained radiation fin
• High outdoor air temperature
Connect correctly.
Eliminate
P4
error.
Keep operating.
Replace the outdoor main
PCB (A1P).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
YES
YES
YES
NO
NO
NO
NO
Is the radiator fin
temperature greater than the
designed temperature?
Does the remote
controller display error
code
P4
?
Does the
connector X111A of fin
thermistor connect to the
outdoor unit PCB
correctly?
When the unit starts
operating, is the error code
L4
displayed again?
Connect to the power and then press
the INSPECTION/TEST button on
remote controller.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...