Troubleshooting by Error Code
Service Diagnosis
186
4.34 Inverter Compressor Startup Abnormality
Error Code
L9
Applicable
Models
All outdoor units
Method of Error
Detection
Error is detected by the power transistor current
Error Decision
Conditions
Compressor overload during activation.
Supposed
Causes
Defective compressor
Large pressure difference before starting the compressor
Defective PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
NO
YES
YES
YES
Does
L9
blink after
reconnecting to the power?
When
operation starts, is the high
and low pressure difference greater than
0.2 MPa (29.0 psi)?
Unbalanced
inverter output voltage (±5 V
is normal). After stabilizing the inverter,
is the inverter output pressure
measurable?
Disconnect the compressor from the
inverter. Use power transistor to check
codes based on maintenance codes.
Nonconforming pressure
balance. Check the
refrigerant system.
Replace the outdoor
main PCB (A1P).
Reset and then restart
the unit.
Check the compressor according to
diagnosis procedure for compressor
abnormal noises/vibrations and
operation conditions.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...