SiUS331604E
Troubleshooting by Error Code
Service Diagnosis
204
Troubleshooting
Is the
power supply of
the indoor unit, on which the
UE
occurred, turned
ON?
For
VRV
systems, can the
setting of centralized control
group No. be made in one and the
same refrigerant
system?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Make correct setting of the
centralized control group No.
Check outdoor units to which
the refrigerant system is
connected.
Check whether or not there
are no problems with the
transmission wiring length,
types of cables and wires,
number of units connected,
and others. If no problems,
replace the indoor unit PCB.
NO
YES
YES
Check the indoor
unit for which
UE
is
displayed. Is the
transmission error
(
UE
) caused on all
indoor units?
NO
NO
YES
Make sure there are no
hazardous situations, and
then turn ON the power
supply.
NO
NO
YES
YES
NO
YES
Reset the power supplies of
every centralized controller.
For the intelligent Touch
controller, register the air
conditioner again while in
DIII-NET test operation menu.
A
Has
the setting of
centralized control
group No. been made with the
indoor unit on which the
UE
occurred?
Can the
setting of centralized
control group No be
made?
Was the
centralized control
group No. for indoor unit
changed?
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...