Special Control
SiUS331604E
43
Functions and Control
3.5
Restart Standby
Restart is forced into standby to prevent the power from frequently turning on and off and to equalize pressure in
the refrigerant system.
Ta: Outdoor air temperature
3.6
Stopping Operation
Actuator operation is cleared when the system is down.
Outdoor unit actuator
Electric symbol
Operation
RXTQ36
TAVJU
RXTQ48
TAVJU
RXTQ60
TAVJU
Compressor
M1C
M1C
M1C OFF
Outdoor fan
M1F
M1F
M1F,
M2F
Ta > 30
°
C (86
°
F): STEP 4
Ta
≤
30
°
C (86
°
F): OFF
Four way valve
Y1S
Y1S
Y1S
Keep former condition.
Main electronic expansion
valve
Y1E
Y1E
Y1E
0 pulse
Subcooling electronic
expansion valve
Y3E
0 pulse
Hot gas bypass valve
Y2S
OFF
Ending conditions
2 minutes
Outdoor unit actuator
Electric symbol
Operation
RXTQ36
TAVJU
RXTQ48
TAVJU
RXTQ60
TAVJU
Compressor
M1C
M1C
M1C OFF
Outdoor fan
M1F
M1F
M1F,
M2F
OFF
Four way valve
Y1S
Y1S
Y1S
Keep former condition.
Main electronic expansion
valve
Y1E
Y1E
Y1E
0 pulse
Subcooling electronic
expansion valve
Y3E
0 pulse
Hot gas bypass valve
Y2S
OFF
Ending conditions
Indoor unit thermostat is turned ON.
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...