SiUS331604E
Protection Control
Functions and Control
44
4. Protection Control
4.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due to an abnormal
increase in high pressure and to protect compressors against transient increases in high pressure.
Cooling operation
Pc > 3.47 MPa (503 psi)
After 10 sec.
Pc > 3.47 MPa (503 psi)
Pc < 3.23 MPa (468 psi)
Pc > 3.64 MPa (528 psi)
Current step maintained
After 15 sec.
High pressure not limited
High pressure limited
Pc: High pressure sensor detection value
Compressor upper limit
frequency: 3-step down from
current compressor frequency
When occurring 10 times within 60
minutes, high pressure switch is activated
without high pressure standby, thus
outputting the error code
E3
.
Compressor upper limit frequency: Maximum
High pressure
standby
Compressor upper limit
frequency: 1-step up from
current compressor frequency