Protection Control
SiUS331604E
47
Functions and Control
4.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature against error or
transient increase in discharge pipe temperature.
•
HTdi > 115˚C (239˚F)
•
Tp > 135˚C (275˚F)
OR
36 Hz Unload
•
HTdi > 115˚C (239˚F)
•
Tp > 135˚C (275˚F)
OR
•
HTdi > 135˚C (275˚F)
•
HTdi > 120˚C (248˚F) for 10 minutes or more.
OR
•
HTdi < 110˚C (230˚F)
•
Tp < 125˚C (257˚F)
&
After 30 seconds
After 20 seconds
•
HTdi > 130˚C (266˚F)
•
HTdi > 120˚C (248˚F)
for 90 seconds
or more.
OR
•
HTdi < 100˚C (212˚F)
•
Tp < 110˚C (230˚F)
&
Discharge pipe
temperature standby
Discharge pipe protection
control not limited
Compressor upper limit
frequency: 1-step down from
current compressor frequency
In discharge pipe temp.
protection control
When occurring 3 times within 100 minutes,
the error code
F3
is output.
Compressor upper limit frequency: 1-step
up from current compressor frequency
Tp: Value of compressor port temperature
calculated by Tc, Te, and suction
superheated degree.
HTdi: Value of compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...