SiUS331604E
Outline of Control (Indoor Unit)
Functions and Control
52
Is
outlet air
temperature drop protection
in progress?
Is test run
in progress?
Restart
prevention operating
in progress?
(4 min.)
Is hot
starting in progress?
Is
defrost operation in
progress?
Program dry operation
Heating Operation
Fan Operation
Thermostat status
A
A
A
OFF
Yes
ON
No
∗
7
∗
8
∗
9
∗
10
∗
11
Thermostat status
No
No
∗
14
∗
15
(Option)
(Option)
(Option)
(Option)
(Option)
(Option)
: OFF
MP
: OFF
52H
Humidifier : OFF
Mu
: OFF
52H
Humidifier : ON
: OFF
Humidifier : OFF
: ON
Humidifier : ON
Mu
52H
Mu
: OFF
52H
Humidifier : OFF
Mu
52H
Mu
(option)
: OFF
MP
Fan :
Operating in L mode
MF
Fan : Operating
in L mode after it stops for 6 min.
MF
20E :
Drain pump kit
20E :
MP
Swing flap
Swing flap
Set wind direction
Fan MF:
Operating with set airflow rate
20E :
Yes
Yes
No
No
No
∗
12
∗
13
∗
12
Yes
Yes
Yes
Swing flap?
Swing flap
Set wind direction
Fan :
Operating with set airflow rate
MF
20E :
20E :
20E :
Fan :
LL operation
MF
Fan :
Operating in L mode
MF
Fan :
Stop
MF
Suction air temperature
b
a
(3)
(2)
(1)
Closed
DEFROST/HOT START
indicating lamp: OFF
Closed
DEFROST/HOT START
indicating lamp: ON
∗
9. Fan operation
By setting the remote controller to Fan, the fan
will operate with thermostat OFF in set
temperature control operation mode.
∗
10. Set wind direction
According to wind direction instruction from the
remote controller, the wind direction is set to
100% horizontal while in heating operation.
∗
11. Fan
According to fan speed instruction from the
remote controller, the fan is put into operation
in LL mode while in heating operation.
∗
12. Wind direction
When the heating thermostat turns OFF, the wind direction will be set to 100% horizontal.
∗
13. Hot start
If the condenser inlet temperature exceeds 34
°
C (93.2
°
F) at the time of starting operation or
after the completion of defrost operation, or until 3 minutes pass or Tc is above 52
°
C (125.6
°
F),
hot starting will be conducted.
∗
14. Thermostat status
∗
15. Outlet air temperature drop protection
When the set temperature is below 24
°
C (75.2
°
F) or the electronic expansion valve opening is
small, the protection will be activated.
Program
dry display
Electronic
expansion valve
Superheated degree control
Electronic
expansion valve
Closed
Drain
pump kit
Electronic expansion valve
Capacity control
Electronic
expansion valve
Open
Electronic
expansion valve
Electronic
expansion valve
Drain
pump kit
: OFF after 5-min.
residual operation
∗
7. Program dry display
No set temperature and airflow rate of the
remote controller are displayed.
∗
8. Thermostat status
Set temperature when operating the program
dry mechanism.
Aux.
electric heater
Aux.
electric heater
Aux.
electric heater
Aux.
electric heater
Aux.
electric heater
–2˚C (28.4˚F)
–4˚C (24.8˚F)
Suction air temp.
Set temp.
b
a
(3)
(2)
(1)
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...