Outline of Control (Indoor Unit)
SiUS331604E
53
Functions and Control
6.2
Set Temperature and Control Temperature
6.2.1 Without the Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is described below.
•
When the suction air thermistor is used for controlling (Default), the control target temperature is determined
as follows to prevent insufficient heating in heating operation.
Control target temperature: remote controller displayed tempe 2°C (3.6°F).
•
The temperature difference for cooling
⇔
heating mode switching is 5°C (9°F).
•
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set temperature.
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...