Outline of Control (Indoor Unit)
Functions and Control
66
6.10 Heater Control (Optional PCB KRP1B series is required.)
Heater control is conducted in the following manner.
Normal control
While in heating operation, heater control (ON/OFF) is
conducted as shown on the right.
Overload control
When the system is overloaded in heating
operation, the heater will be turned OFF in the
following two manners.
(1) Heater control (ON/OFF) is conducted through
the liquid pipe temperature (R2T) of the indoor
unit.
(2) Heater control (ON/OFF) is conducted by
converting the heater temperature into the
condensing pressure equivalent saturated
temperature (Tc) according to the temperature
detection through the high pressure sensor
(S1NPH) of the outdoor unit.
Fan residual operation
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan conducts residual
operation for a given period of time after the heater turns OFF. (This operation is conducted regardless of
whether or not a heater is equipped.)
Residual operation time: 100 seconds on ceiling suspended type or 60 seconds on other types
ON
Set temperature
OFF
2ºC
(3.6˚F)
2ºC
(3.6˚F)
ON
43ºC
(109.4˚F)
50ºC
(122˚F) Liquid pipe temperature
OFF
ON
50ºC
(122˚F)
60ºC
(140˚F)
OFF
Condensing pressure
equivalent saturated
temperature
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...