Test Operation
SiUS331604E
73
Field Setting
1. Test Operation
Follow the following procedure to conduct the initial test operation after installation.
1.1
Check Work Prior to Turning Power Supply ON
1.2
Turn Power ON
Check on refrigerant piping /
insulation material
Check on amount of refrigerant
charge
Check the below items.
•
Power wiring
•
Control transmission wiring
between units
•
Earth wire
•
Is the power supply appropriate?
•
Have you finished a ductwork to drain?
•
Have you detach transport fitting?
•
Is the wiring performed as specified?
•
Are the designated wires used?
•
Is the grounding work completed?
Use a 500 V Megger tester to measure the insulation.
Do not use a Megger tester for low voltage circuits.
•
Are the setscrews of wiring not loose?
•
Is the electrical component box covered with an insulation cover
completely?
•
Is refrigerant charged up to the specified amount?
If insufficient, charge the refrigerant from the service port of stop
valve on the liquid side with outdoor unit in stop mode after turning
power ON.
•
Has the amount of refrigerant charge been recorded on “Record
Chart of Additional Refrigerant Charge Amount”?
•
Is pipe size proper? (The design pressure of this product is 4.0
MPa (580 psi).)
•
Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes
water leak.)
•
Are respective stop valves on liquid and gas line securely open?
Turn outdoor unit power ON.
Turn indoor unit power ON.
•
Be sure to turn the power ON 6 hours before starting operation to
protect compressors.
•
Close outside panels of the outdoor unit.
Carry out field setting on
outdoor PCB
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...