Field Setting from Remote Controller
Field Setting
84
Note:
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside
parentheses, you can also set units individually. Setting changes however cannot be checked except in the
individual mode in parentheses.
∗
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they cannot be set
individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the indoor unit is
not equipped with.
4.
88
or
Checking the connection. Please stand by
. may be displayed to indicate that the remote controller is
resetting when returning to normal mode.
∗
5. If the setting mode is set to Equipped, heat reclaim ventilation fan conducts the fan residual operation by
linking to the indoor unit.
∗
6. Only for FXTQ
∗
7. For FXTQ: Factory setting is
02
.
∗
8.
13(23)
0
Setting of normal airflow
N
H
S
—
(19)
1
Selection of airflow direction
(Set when a sealing material kit has been installed.)
F (4 directions)
T (3 directions)
W (2
directions)
—
(20)
2
Swing pattern settings
(In case of an infrared floor sensor is installed)
All direction
synchronized
swing
—
Facing swing
—
(21)
3
Operation of downward flow flap
Equipped
Not equipped
—
—
(22)
4
Setting airflow position
Draft prevention
Standard
Ceiling
Soiling
prevention
—
(23)
5
Setting of static pressure selection
Standard
High static
pressure
—
—
(24)
6
External Static Pressure Settings
Refer to page 94.
(25)
14
(24)
4 (
∗
6)
Setting of Humidifier / Air Purifier Fan Tap
Remote
controller setting
H tap
—
—
(26)
5 (
∗
6)
Residual Operation Time
30 seconds
60 seconds
120 seconds
—
(27)
15(25)
1
Thermostat OFF excess humidity
Not equipped
Equipped
—
—
(28)
2
Direct duct connection
(when the indoor unit and Heat Reclaim
Ventilator are connected by duct directly.) (
∗
5)
Not equipped
Equipped
—
—
(29)
3
Drain pump and humidifier interlock selection
Not equipped
Equipped
—
—
(30)
5
Selection for individual ventilation setting by
remote controller
Not equipped
Equipped
—
—
(31)
1b (2b)
3
Display of Contact Center
Displayed
Not displayed
—
—
(32)
4
Display of error codes on the remote controller
—
Two-digit display
—
Four-digit
display
(33)
12
Key-lock pattern settings
No operation
allowed (Cancel
procedure is
displayed.)
No operation
allowed (Cancel
procedure is not
displayed.)
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
No menu
operation is
allowed any
time.
(34)
14
Setting restricted/permitted for airflow block
Refer to page 96.
(35)
1c (2c)
0
Room temperature display
Room
temperature is
not displayed
Room
temperature is
displayed
—
—
(36)
Mode
No.
(
∗
2)
First
Code
No.
Description
Second Code No.
Details
No.
01
02
03
04
Set temperature
<Ttsoff>
<Ttson>
Thermostat
OFF
Thermostat
ON
Summary of Contents for VRV IV-S RXTQ-TAVJU Series
Page 1: ...Service Manual SiUS331604E RXTQ36 48 60TAVJU Heat Pump 60 Hz...
Page 254: ...Wiring Diagrams SiUS331604E 241 Appendix RXTQ48TAVJU 3D100496A...
Page 255: ...SiUS331604E Wiring Diagrams Appendix 242 RXTQ60TAVJU 3D100497A...
Page 260: ...Wiring Diagrams SiUS331604E 247 Appendix FXEQ07 09 12 15 18 24PVJU C 3D098557...
Page 267: ...SiUS331604E Wiring Diagrams Appendix 254 FXTQ12 18 24 30 36 42 48 54PAVJU 3D065036G...
Page 270: ...Wiring Diagrams SiUS331604E 257 Appendix VAM1200GVJU 3D073270C...
Page 271: ...Revision History Month Year Version Revised contents 06 2016 SiUS331604E First edition...