Troubleshooting
Service manual
109
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.94 L1-36-38-40 – Inverter PCB A3P Eeprom error
Main error code
Sub error code
Unit
L1
36
Main
38
Sub 1
40
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A3P fails
reading/writing memory
(EEPROM error).
Unit will stop operating.
Manual reset via user
interface.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the inverter PCB A3P. See
Possible cause:
Faulty inverter PCB A3P or non‑compatible inverter PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.95 L1-37-39-41 – Inverter PCB A6P Eeprom error
Main error code
Sub error code
Unit
L1
37
Main
39
Sub 1
41
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.