2
|
Troubleshooting
Service manual
131
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.117 LC-33-34-35 – Transmission abnormality main PCB/sub PCB
Main error code
Sub error code
Unit
LC
33
Main
34
Sub 1
35
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
No transmission between
main PCB and sub PCB.
Unit will stop operating.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB or wrong capacity setting.
2
Perform a check of the Sub PCB. See
342].
Possible cause:
Faulty Sub PCB.
3
Check the wiring between the PCB's. See
Possible cause:
Faulty wiring between PCB's.
4
Check if the correct spare part is installed for all PCB's. See checking
procedures of the specific PCB's.
Possible cause:
Wrong spare part PCB installed.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.118 P1-01-02-03 – Open phase or unbalanced power supply detection by inverter PCB A3P
Main error code
Sub error code
Unit
P1
01
Main
02
Sub 1
03
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Summary of Contents for VRV IV+