2
|
Troubleshooting
Service manual
159
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.153 U3-07 – Transmission abnormality on test run
Trigger
Effect
Reset
Test run could NOT start
or abort due to
transmission issues.
Unit will NOT operate.
Restart test run.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if communication between outdoor unit and indoor units is initialised.
Check field setting 1‑10 for count of indoor units, see
455]. If less indoor units shown than expected, communication
between 1 or more indoor unit(s) and outdoor unit is NOT correct. Check the
F1‑F2 transmission line between the indoor unit and outdoor unit, see
356].
Possible cause:
Faulty or interruption in transmission line between indoor
units and outdoor unit.
2
Check the F1‑F2 transmission line between the indoor units and outdoor unit.
See
Possible cause:
Faulty or interruption in transmission line between indoor
units and outdoor unit.
3
Perform a test run from the outdoor unit. See installer reference guide for
more information.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.154 U3-08 – Transmission abnormality on test run
Trigger
Effect
Reset
Test run could NOT start
or abort due to
transmission issues.
Unit will NOT operate.
Restart test run.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if communication between outdoor unit and indoor units is initialised.
Check field setting 1‑10 for count of indoor units, see
455]. If less indoor units shown than expected, communication
between 1 or more indoor unit(s) and outdoor unit is NOT correct. Check the
F1‑F2 transmission line between the indoor unit and outdoor unit, see
356].
Possible cause:
Faulty or interruption in transmission line between indoor
units and outdoor unit.
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......
Page 476: ...ESIE18 15B 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...