2
|
Troubleshooting
Service manual
166
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
3
Perform a check of the main PCB of the sub 1 outdoor unit. See
290].
Possible cause:
Faulty main PCB of the sub 1 outdoor unit.
4
Perform a check of the main PCB of the sub 2 outdoor unit. See
290].
Possible cause:
Faulty main PCB of the sub 2 outdoor unit.
5
Check that ONLY the master outdoor unit has F1‑F2 IN connection. If another
outdoor unit has F1‑F2 IN connection, correct the installation.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.163 U7-06 – Multi system address abnormality
Trigger
Effect
Reset
Main PCB on main
outdoor unit detects
transmission abnormality
on a multi installation.
Forced stop.
Auto reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the Q1‑Q2 communication between the outdoor units. See
Possible cause:
Faulty or interruption in communication between outdoor
units.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
3
Check that ONLY the master outdoor unit has F1‑F2 IN connection. If another
outdoor unit has F1‑F2 IN connection, correct the installation.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.164 U7-07 – More than 3 outdoor units on Q1-Q2 transmission
Trigger
Effect
Reset
More than 3 outdoor
units are detected on Q1-
Q2 transmission line.
Forced stop.
Power reset at outdoor
unit.