2
|
Troubleshooting
Service manual
172
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.174 UA-20 – Combination abnormality - Non-compatible outdoor unit in multi-combination
Trigger
Effect
Reset
Main PCB on main
outdoor unit detects
compatibility issues.
Forced stop.
Automatic reset after
re‑initialization detects
compatible units.
Outdoor unit NOT
compatible with multi
combination.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for improper combination of units. See the combination table in the
Databook for more information. Change the installation with ONLY compatible
type units.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.175 UA-21 – Combination abnormality - BPMK units detected
Trigger
Effect
Reset
Main PCB detects BPMK
unit(s) on F1/F2 wiring.
Forced stop.
Automatic reset after re-
initialization detects
compatible units.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for improper combination of units. See the combination table in the
Databook for more information. Change the installation with ONLY compatible
type units.
2
Change the installation without BPMK units.
2.3.176 UA-22 – Combination abnormality - Single Installation
Trigger
Effect
Reset
Abnormal combination on
outdoor unit installation.
Unit will not operate.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.