2
|
Troubleshooting
Service manual
178
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
REMQ-U unit installed as standalone unit.
4
Perform a check of the main PCB of the main outdoor unit. See
290].
Possible cause:
Faulty main PCB of the main outdoor unit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.185 UA-35 – Combination abnormality - REMQ-U Unit Detected in Wrong Combination
Trigger
Effect
Reset
REMQ Unit detected in a
Not-Allowed combination
Unit will stop operating
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
REMQ Units are only allowed in multi combination as REMQ5U or
REMQ5U.
Possible cause:
REMQ-U unit installed in a not-allowed multi combination.
2
Check the Q1‑Q2 communication between the outdoor units in multi
combination. See
356].
Possible cause:
Faulty wiring.
3
Perform a check of the main PCB of the main outdoor unit. See
290].
Possible cause:
Faulty main PCB of the main outdoor unit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.186 UA-38 – Combination abnormality - Altherma hydro unit detected
Trigger
Effect
Reset
Main PCB on main
outdoor unit detects
Altherma hydrobox on F1-
F2 IN wiring.
Forced stop.
Automatic reset after re-
initialization detects
compatible units.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Only LT Hydrobox HXY-A and HT Hydrobox HXHD-A are allowed in the
installation. See the Databook for more information.