2
|
Troubleshooting
Service manual
180
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for improper combination of units. See the combination table in the
Databook for more information. Change the installation with ONLY compatible
type units.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.190 UA-50 – Combination abnormality - High Temperature Hydrobox Detected Connected to a
BS Unit
Trigger
Effect
Reset
HXHD-A unit detected on
branch selector box to
indoor F1-F2 wiring.
Forced stop.
Power reset at outdoor
unit.
To solve the error code
1
HXHD-A units are not allowed to connect under BS Unit piping. Check HXHD-A
unit installation manual.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.191 UA-51 – Combination abnormality - Only Hydrobox Units Detected
Trigger
Effect
Reset
Outdoor unit detects only
hydro units connected.
Forced stop.
Power reset at outdoor
unit.
To solve the error code
1
System must detect at least 50% VRV indoor units connected through branch
selector boxes. Refer to databook. Modify system layout.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.192 UA-53 – Combination abnormality - Branch Selector box Dip Switch Abnormality
Trigger
Effect
Reset
Branch selector box dip
switch abnormality is
detected.
Forced stop.
Power reset at outdoor
unit.