2
|
Troubleshooting
Service manual
183
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.195 UF-11 – Wiring and piping mismatch - Excess connection ratio
Trigger
Effect
Reset
Minimum 1 indoor unit
fails to perform cross pipe
check during test run.
Forced stop.
Perform test run.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check that the refrigerant circuit piping and wiring connections of the system
are correctly installed.
Possible cause:
Refrigerant piping and/or wiring mismatch.
3
Set field setting 2‑5 of the outdoor unit to 1 to start the indoor units
connected to that outdoor unit on forced fan operation, see
455]. If any of these indoor units is NOT operating, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
4
Check field setting 1‑10 to count the indoor units, see
455]. If less indoor units detected than it should be, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
5
Perform a check of the indoor unit pipe thermistors, see service manual of the
respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit pipe thermistor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.196 UH-01 – Auto-address failure
Trigger
Effect
Reset
Main PCB detects
improper combination at
indoor unit side.
Forced stop.
Reset communication
from main PCB.
Missing auto address of
indoor unit(s) after
initialization.
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......
Page 476: ...ESIE18 15B 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...