2
|
Troubleshooting
Service manual
195
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Main
code
Sub code
Description
Main Sub 1 Sub 2
U2
01
08
11
Inverter Circuit Power Supply Abnormality - Inverter PCB (A3P) Abnormal Voltage
02
09
12
Inverter Circuit Power Supply Abnormality - Inverter PCB (A3P) Phase Loss
03
10
13
Inverter Circuit Power Supply Abnormality - Inverter PCB (A3P) DC Circuit Not
Charging
22
25
28
Inverter Circuit Power Supply Abnormality - Inverter PCB (A6P) Abnormal Voltage
23
26
29
Inverter Circuit Power Supply Abnormality - Inverter PCB (A6P) Phase Loss
24
27
30
Inverter Circuit Power Supply Abnormality - Inverter PCB (A6P) DC Circuit Not
Charging
U3
02
Test Run failed due to unit error
03
Test Run Not Performed Yet
04
Test Run Ended Abnormally
05
Test Run Aborted on Initial Transmission
06
Test Run Aborted on Normal Transmission
07
Transmission abnormality on Test Run
08
Transmission abnormality on Test Run
U4
01
Transmission Error between Indoor U and Outdoor Unit
03
Transmission Error between Indoor U and System
15
Unable to Start Test Run
U7
01
Transmission Abnormality Between Systems - DTA104A61, DTA104A62 Error
02
Transmission Abnormality Between Systems - DTA104A61, DTA104A62 Error
03
Transmission Error Between Main Outdoor Unit and Sub 1 Outdoor Unit
04
Transmission Error Between Main Outdoor Unit and Sub 2 Outdoor Unit
05
Multi System Abnormality
06
Multi System Address Abnormality, Error in Address Setting for Sub 1 and Sub 2
Units
07
More Than 3 Outdoor Units on Q1-Q2 Transmission
11
Excess Indoor Units Detected on Test Run
24
Duplication of Address Setting on Multiple DTA104A61,62 Installation
Summary of Contents for VRV IV+