2
|
Troubleshooting
Service manual
198
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.4 Symptom based troubleshooting
2.4.1 Normal operating conditions
Below items are a guideline on how to check normal operating conditions of the
unit. Still, values are for reference ONLY and working conditions outside of this
range do NOT necessarily address abnormalities and errors. Operating conditions
are a result of several items to check together.
Item
Description
Normal value
Discharge superheat
Discharge pipe
temperature –
condensation
temperature
25 K to 45 K
Discharge superheat = discharge pipe temperature – condensation temperature
▪
Discharge pipe temperature: Read out from discharge pipe thermistor R21T/
R22T depending on the compressor.
▪
Condensation temperature: Calculated by main PCB from the pressure
read‑out of the high pressure sensor.
Higher discharge superheat may result from refrigerant shortage or compressor
internal by‑pass.
Lower discharge superheat may result from low suction superheat which is caused
by wet operation.
Item
Description
Normal value
Suction superheat
Suction temperature –
evaporation temperature
5 K
Suction superheat = suction temperature – evaporation temperature
▪
Suction temperature: Read out from suction thermistor R3T
▪
Evaporation temperature: Calculated by main PCB from the pressure
read‑out of the low pressure sensor.
Suction superheat may be high if difference between [indoor set temperature –
indoor air temperature] is too high and will result in high discharge superheat.
Suction superheat may be low if:
▪
Difference between [indoor set temperature – indoor air temperature] is too low
▪
Discharge superheat is too low (<20 K)
▪
Outdoor unit judges wet operation
2.4.2 Symptom: The system does not operate
▪
The air conditioner does not start immediately after the ON/OFF button on the
user interface is pressed. If the operation lamp lights, the system is in normal
condition. To prevent overloading of the compressor motor, the air conditioner
starts 5 minutes after it is turned ON again in case it was turned OFF just before.
The same starting delay occurs after the operation mode selector button was
used.
▪
If "Under Centralized Control" is displayed on the user interface, pressing the
operation button causes the display to blink for a few seconds. The blinking
display indicates that the user interface cannot be used.