Troubleshooting
Service manual
203
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Symptom
Possible failure
Root cause
Repair
Operation stops and then
restarts after 3 minutes.
Outdoor unit performing
'retry' operation
Retry mode triggered by an
error
Check field setting 1-23,
1-24, 1-25 for latest retry
content. See
455]. Refer to
error code found for
further troubleshooting.
Unit operates but does not
cool or does not heat
Piping or wiring mismatch
Tranmission or piping
problem
Correct piping, wiring
Abnormal refrigerant
amount
Outdoor unit may be
overcharged or lacking
refrigerant
Check refrigerant amount.
See
Incorrect thermistor values Thermistors not in their
location, miswiring or
faulty thermistor
Check thermistors, see
Incorrect expansion valve
operation
Expansion valve not
operating correctly
Check expansion valves.
See
Cross piping/wiring among
different outdoor unit
systems
Indoor unit transmission
line and piping is not
connected to the same
outdoor unit system
Correct piping, wiring