Troubleshooting
Service manual
24
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Main PCB detects earth
leakage through current
sensor >safety value, see
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the current sensor. See
Possible cause:
Faulty current sensor.
2
Check if the power supply is conform with the regulations. See
356].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
4
Using a megger device, check the solenoid valve coils, 4‑way valve coil, fan
motors and compressors if any earth leakage is found. Replace the
component(s) that generate earth leakage.
5
Check if the refrigerant circuit is correctly charged. See
363].
Possible cause:
Refrigerant overcharge.
6
Check for the presence of humidity in the refrigerant circuit. See
363].
Possible cause:
Humidity in the refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.5 E2-06-07-08 – Open circuit on earth leakage detection core
Main error code
Sub error code
Unit
E2
06
Main
07
Sub 1
08
Sub 2