Troubleshooting
Service manual
25
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Main PCB detects open
circuit on connector
X101A.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that connector X101A is correctly connected to the main PCB. See
290].
Possible cause:
Open circuit on connector X101A.
2
Perform a check of the current sensor. See
237].
Possible cause:
Faulty current sensor.
3
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.6 E3-01-03-05 – Actuation of high pressure switch
Main error code
Sub error code
Unit
E3
01
Main
03
Sub 1
05
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.