3
|
Components
Service manual
260
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Is the measured output voltage on the
inverter PCB correct?
Action
Yes
Correct the wiring between the fan
inverter PCB and the inverter PCB, see
361].
No
Perform a check of the inverter PCB,
see
To check the HAP LED of the fan inverter PCB
1
First perform a power check of the fan inverter PCB, see
2
Locate the HAP LED on the fan inverter PCB.
a
a
HAP LED
Does the HAP LED blink in regular
intervals (approximately 1 Hz)?
Action
Yes
PCB and continue with the next
procedure.
No
Replace the fan inverter PCB, see
263].
To check if the correct spare part is installed
Prerequisite:
First perform all earlier checks of the fan inverter PCB, see
1
Visit your local spare parts webbank.
2
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.
Is the correct spare part for the fan
inverter PCB installed?
Action
Yes
PCB and continue with the next
procedure.