3
|
Components
Service manual
263
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the fan inverter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
Prerequisite:
315].
1
Locate the fan inverter PCB.
2
Using pliers, detach the cable clamp from the power terminal assembly.
a
a
b
a
Cable clamp
b
Fan connector X1A
3
Disconnect the fan connector X1A from the fan inverter PCB.
a
b
b
a
d
c
a
a
a
Connector
b
Screw
c
Connector X1A
d
Connector X4A
4
Disconnect all other connectors from the fan inverter PCB.
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......
Page 476: ...ESIE18 15B 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...