3
|
Components
Service manual
269
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
a
Fan inverter PCB A4P
b
Fan inverter PCB A7P
c / c'
Connector P11
d / d'
Connector N11
e / e'
Connector X1A, pin U
f / f'
Connector X1A, pin V
g / g'
Connector X1A, pin W
VDC
Com
Ref
VDC
Com
Ref
P11
X1A, pin U
O.L
N11
X1A, pin V
0,45
P11
X1A, pin V
O.L
N11
X1A, pin W
0,45
P11
X1A, pin W
O.L
X1A, pin U
N11
O.L
X1A, pin U
P11
0,45
X1A, pin V
N11
O.L
X1A, pin V
P11
0,45
X1A, pin W
N11
O.L
X1A, pin W
P11
0,45
P11
N11
O.L
N11
X1A, pin U
0,45
N11
P11
0,75
Are the test results OK?
Action
Yes
Power transistors are OK. Return to
265].
No
Replace the fan inverter PCB, see
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the fan inverter PCB
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
315].
a
b
b
a
d
c
a
a
a
Connector
b
Screw
c
Connector X1A
d
Connector X4A