3
|
Components
Service manual
291
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
a
a
Connector X37A
Is the measurement correct?
Action
Yes
Return to
290] of the main PCB
and continue with the next procedure.
No
Replace the main PCB, see
293].
To check the HAP LED of the main PCB
Prerequisite:
First perform a power check of the main PCB, see
290].
1
Locate the HAP LED on the main PCB.
a
a
HAP LED
Does the HAP LED blink in regular
intervals (approximately 1 Hz)?
Action
Yes
Return to
290] of the main PCB
and continue with the next procedure.
No
293].
To check if the correct spare part is installed
1
First perform all earlier checks of the main PCB, see
290].
2
Visit your local spare parts webbank.
3
Enter the model name of your unit and check if the installed spare part
number corresponds with the spare part number indicated in the webbank.