3
|
Components
Service manual
295
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
b
a
a
a
a
a
a
a
a
a
c
c
c
c
c
c
c
c
a
Connector
b
Wire terminal
c
PCB support
3
Connect all connectors to the main PCB assembly.
d
e
d
Connector X40A
e
Connector X41A
4
Pay attention to connectors X40A and X41A when re-connecting wiring: the
black/white wiring should be connected to X40A and the red/black wiring
should be connected to X41A.
5
Connect all the wire terminals.
6
When installing a new main PCB , it needs to be defined for capacity.
Otherwise, PJ error is generated.
7
When installing a new main PCB, set the dipswitch settings accordingly to the
model. See
293].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
290] of the main PCB
and continue with the next procedure.