2
|
Troubleshooting
Service manual
34
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
7
Check liquid back issue. Check expansion valve operation. See
244].
Possible cause:
Expansion valve CANNOT keep minimum superheat of 3 K
while running as evaporator.
8
Check if the refrigerant circuit is correctly charged. See
363].
Possible cause:
Refrigerant shortage.
9
Perform a check of the 4‑way valve. See
206].
Possible cause:
Faulty 4‑way valve.
10
Perform
a
check
of
the
discharge
pipe
thermistor.
See
Possible cause:
Faulty discharge pipe thermistor or connector fault.
11
Perform a check of the inverter PCB A3P. See
274].
Possible cause:
Faulty inverter PCB A3P.
12
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.14 E5-07-08-09 – Compressor overload/Motor Lock Error (M2C)
Main error code
Sub error code
Unit
E5
07
Main
08
Sub 1
09
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Compressor overload is
detected for M2C.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
363].
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Check if the refrigerant circuit is clogged. See
363].