3
|
Components
Service manual
350
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Name
Symbol
Location (PCB) Connector
(pins)
Type
Compressor
(M1C for
REYQ8~12U,
M2C for
20U)
Body
Thermistor
R15T
Main
X19A: 5-6
2
Compressor
M1C Discharge
Thermistor
R21T
Main
X19A:1-2
2
Compressor
M2C discharge
thermistor
R22T
Main
X19A:3‑4
2
4
Determine the thermistor resistance that matches the measured
temperature.
Type 1 thermistor
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
–20
197.81
10
39.96
40
10.63
70
3.44
–19
–18
–17
–16
–15
–14
–13
–12
–11
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
11
12
13
14
15
16
17
18
19
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
41
42
43
44
45
46
47
48
49
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
71
72
73
74
75
76
77
78
79
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
–10
111.99
20
25.01
50
7.18
80
2.47