4
|
Third party components
Service manual
361
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To check the wiring between the outdoor unit and the indoor unit
1
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2
Check that no connectors or wires are damaged.
3
Check that the wiring corresponds with the wiring diagram, see
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.1.2 Repair procedures
To adjust the power supply
1
Make sure that the power source is in line with the requirements described in
the databook.
2
Adjust the power supply within 50 Hz ± 3%.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To adjust the wiring between the outdoor unit and the indoor unit
1
Adjust the wiring according to the wiring diagram and connection diagram,
see
2
Check that all wires are properly connected and that all connectors are fully
plugged‑in.
3
Check that no connectors or wires are damaged.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.