Troubleshooting
Service manual
39
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.18 E7-02-14-26 – Outdoor unit fan motor M2F error
Main error code
Sub error code
Unit
E7
02
Main
14
Sub 1
26
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Malfunction of rotation
detection for M2F.
Careful, there is no rpm
detection. Fan judgement
is based on logic by
current drawn.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the fan inverter PCB A7P. See
Possible cause:
Faulty fan inverter PCB A7P.
2
Check if power supply cable to fan motor is NOT loose. Check connector X2A
on fan inverter PCB A7P. See "To check the wiring of the fan inverter PCB"
259]. Check wire to fan motor M2F.
Possible cause:
Faulty power supply cable to fan motor M2F.
3
Perform a check of the outdoor unit fan motor M2F. See
307].
Possible cause:
Faulty outdoor unit fan motor M2F.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.19 E7-05-17-29 – Outdoor unit fan motor M1F overcurrent error
Main error code
Sub error code
Unit
E7
05
Main
17
Sub 1
29
Sub 2